EasyManua.ls Logo

Allen-Bradley PowerFlex 700S - Page 112

Allen-Bradley PowerFlex 700S
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
112 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
Frame Voltage
Class
ND/HD
Rating
(Amps)
Frequency
(kHz)
(1)
(1) Not all frequencies can be run on all drives.
Ambient Temp (C)
(2)
(2) Ambient Temp / Max. Surrounding Air Temperature is the air temperature surrounding the drive module. Rated temperature is 40/40 C (ND/HD) for 400V class drives and 35/35 C (ND/HD) for 600V class drives.
Derate
(2)
11 400 730/650 PWM 50 35 20
1.5 645 780 886
2.0 630 770 856
4.0 473 586 682
6.0 377 477 564
8.0 309 400 477
10.0 264 341 400
600 590/502 PWM 50 35 20
1.5 460 595 690
2.0 455 590 686
4.0 273 364 441
6.0 195 273 336
8.0 150 218 264
10.0 123 177 218
20
25
30
35
40
45
50
55
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750
Iout (Amps)
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
Max. Surrounding Air Temperature °C
20
25
30
35
40
45
50
55
0 50 100 150 200 250 300 350 400 450 500 550 600 650
Iout (Amps)
1.5 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
Max. Surrounding Air Temperature °C