48 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
Control Terminal Block Specifications
TB1 Terminals
TB2 Terminals
Terminal Signal Factory Default Description Related Parameter
1 Analog Input 1 Comm. (Volt) Bipolar, differential input, +/-10V, 0…20 mA, 13 bit + sign
20k Ohm impedance at Volt; 500 Ohm impedance at mA
(1)
(1) The Analog inputs are not isolated. However, the analog inputs can be connected in series when using current mode. Note that at 20 mA the voltage source must be capable of providing 10V DC at the drive terminals for one drive
- - 20V DC is required for two drives and 30V DC is required for three drives, and so on.
2 Analog Input 1 (+/-) 800
3 Shield NA Analog Input Shield
4 Analog Input 2 Comm. (Volt) Bipolar, differential input, +/-10V, 0…20 mA, 13 bit + sign
20k Ohm impedance at Volt; 500 Ohm impedance at mA
(1)
5 Analog Input 2 (+/-) 806
6 Analog Input 3 [NTC-]
Comm.
(Volt) Differential input, 0…10V, 10 bit (for motor control mode FOC2, this is the
temperature adaptation input).
(1)
7 Analog Input 3 [NTC+] 812
8 Shield NA Analog Output Shield
9 Analog Output 1 (-) (Volt) Bipolar, differential output, +/-10V, 0…20 mA, 11 bit + sign
2k Ohm minimum load
832, 833
10 Analog Output 1 (+)
11 Analog Output 2 (-) (Volt) 839, 840
12 Analog Output 2 (+)
13 +10V Reference NA Rating: 20 mA maximum load (Recommend 5k Ohm pot)
14 Reference Common NA
15 -10V Reference NA
16 Encoder A NA Normal current draw per channel: 20 mA 230…234
17 Encoder A (Not) NA
18 Encoder B NA
19 Encoder B (Not) NA
20 Encoder Z NA
21 Encoder Z (Not) NA
22 Encoder Reference (+) NA 12V or 5V DC power supply for primary encoder interface
Rating: 300 mA maximum
23 Encoder Reference (-) NA
24 Encoder Shield NA Connection point for encoder shield
Terminal Signal Factory Default Description Related Parameter
1 24V DC Common (-) NA Drive supplied 24V DC logic input power
Rating: 300 mA maximum load
2 24V DC Source (+) NA
3 Digital Output 1 24V DC Open Collector (sinking logic)
Rating: Internal Source = 150 mA max.
External Source = 750 mA
846, 847
4 Digital Output 1/2 Com NA Common for Digital Output 1 & 2
5 Digital Output 2 24V DC Open Collector (sinking logic)
Rating: Internal Source = 150 mA max.
External Source = 750 mA
851, 852
6 Relay Output 3 (NC) Relay contact output
Rating: 115V AC or 24V DC = 2 A max.
Inductive/Resistive
856, 857
7 Relay Output 3 Com NA
8 Relay Output 3 (NO)
9 Digital Input 1-3 Com NA Common for Digital Inputs 1-3
10 Digital Input 1 High speed 12V or 24V DC
(1)
sinking
Load:15 mA at 24V DC
(1) Digital Inputs 1 and 2 are configured for 12V or 24V DC via DIP switches S3-1 and S3-2, respectively. 24V DC is the default setting.
825
11 Digital Input 2 826
12 Digital Input 3 Load:15 mA at 24V DC sourcing 827
13 Digital Input 4-6 Com NA Common for Digital Inputs 4-6
14 Digital Input 4 Load: 10 mA at 24V DC sinking/sourcing
Load: 7.5 mA at 115V AC
Note: The 115V AC Digital Inputs can withstand 2 milliamps of leakage current
without turning on. If an output device has a leakage current greater than 2
milliamps a burden resistor is required. A 68.1K ohm resistor with a 0.5 watt rating
should be used to keep the 115V AC output below 2 milliamps.
828
15 Digital Input 5 829
16 Digital Input 6 HW Enable 830
1
2
3
4
5
6
7
8
9
12
10
11
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16