56 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
690 Volt AC Input Frames 5 & 6 Drive Ratings
20DE750 12 800 – 2 40 724 750 825 1170 10570
– 700 2 40 628 650 975 1170 10570
20DE820
(1)
12 900 – 2 35 792 820 902 1170 11082
– 700 2 35 628 650 975 1170 11082
20DE920 13 1000 – 2 40 888 920 1012 1380 12690
– 900 2 40 792 820 1230 1410 12690
20DE1K0 13 1100 – 2 40 994 1030 1133 1545 15907
– 1000 2 40 888 920 1380 1755 15907
20DE1K1 13 1300 – 2 35 1139 1180 1298 1755 17306
– 1100 2 35 994 1030 1463 1755 17306
20DE1K5 14 1600 – 2 40 1448 1500 1650 2250 22500
– 1400 2 40 1255 1300 1950 2340 22500
(1) 20DE820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2) Maximum air temperature surrounding the drive module.
Drive Catalog
Number
Frame
kW Rating PWM
Freq.
Temp.
(1)
(1) UL Type 12/IP54 (flange mount) heatsink ambient temperature rating is 40 °C ambient of unprotected drive portion (inside enclosure) is 55 C. The ambient
temperature for the UL Type 12/IP54 standalone drives is 40 C.
Input Ratings Output Amps Watts
Loss
ND HD kHz C Amps kVA Cont. 1 Min. 3 Sec.
20DF052 5 45 – 4 50 46.9 59.5 52 57 78 1084
– 37.5 4 50 40.1 48.0 46 69 92 1084
20DF060 5 55 – 4 50 57.7 68.9 60 66 90 1300
– 45 4 50 46.9 59.5 52 78 104 1300
20DF082 5 75 – 2 50 79.0 94.4 82 90 123 1462
– 55 2 50 57.7 68.9 60 90 120 1462
20DF098 5 90 – 2 40 94.7 113 98 108 127 1846
– 75 2 40 79.0 94.4 82 123 140 1846
20DF119 6 110 – 2 50 115 138 119 131 179 1832
– 90 2 50 92.9 113 98 147 196 1832
20DF142 6 132 – 2 50 139 165.9 142 156 213 2253
– 110 2 40 115 137 119 179 238 2253
600 Volt AC Input Frames 9…14 Drive Ratings (continued)
Drive Catalog
Number
Frame
HP Rating PWM
Freq.
Temp.
(2)
Input
Ratings
Output Amps Watts
Loss
ND HD kHz C Amps Cont. 1 Min. 3 Sec.