EasyManua.ls Logo

Allen-Bradley PowerFlex 700S - Page 58

Allen-Bradley PowerFlex 700S
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
325 Volt DC Input Frames 1…6 Drive Ratings
540 Volt DC Input Frames 1…6 Drive Ratings
Drive Catalog
Number
Frame
HP Rating PWM Freq. Temp.
(3)
(3) The temperature rating that is listed for frame size 1…4 drives is for NEMA/UL open types only. The adhesive tape label must be removed in order to operate at this
temperature, otherwise the ambient operating temperature of these drives is 40 °C.
DC Input Ratings Output Amps
(4)
(4) Frame 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy-duty applications (in parentheses). The drive may be operated
at either rating.
Watts
Loss
ND HD kHz C Amps Cont. 1 Min. 3 Sec.
20DB015 1 5 3 4 45 16 15.3 16.8 23.0 200
20DB022 1 7.5 5 4 45 23.3 22 24.2 33 218
20DB028 2 10 7.5 4 45 30 28 33 44 267
20DB042 3 15 10 4 45 45 42 46.2 63 359
20DB052 3 20 15 4 45 55 52 63 80 414
20DB070 4 25 20 4 45 75.3 70 78 105 629
20DB080 4 30 25 4 45 85.8 80 105 140 777
20DN104
(1)
(1) Catalog number corresponds to output amps for these drives. Drive must be programmed to lower voltage to obtain higher currents that are shown at right.
5 40 30 4 45 114.1 104 (80) 115 (120) 175 (160) 855
20DN130
(1)
5 50 40 4 45 142.6 130 (104) 143 (156) 175 (175) 1041
20DN154
(1)
6 60 50 4 45 169 154 (130) 169 (195) 231 (260) 1260
20DN192
(1)
6 75 60 4 45 210.6 192 (154) 211 (231) 288 (308) 1671
20DN260
(1)(2)
(2) Catalog number corresponds to drives with precharge only.
6 100 75 4 50 272.1 260 (205) 286 (305) 390 (410) 1867
Drive Catalog
Number
Frame
kW Rating PWM Freq. Temp.
(2)
(2) The temperature rating that is listed for frame size 1…4 drives is for NEMA/UL open types only. The adhesive tape label must be removed in order to operate at this
temperature, otherwise the ambient operating temperature of these drives is 40 °C.
DC Input Ratings Output Amps Watts
Loss
ND HD kHz C Amps Cont. 1 Min. 3 Sec.
20DC3P5 1 1.5 1.1 4 50 3.7 3.5 4.5 6.0 112
20DC5P0 1 2.2 1.5 4 50 5.3 5.0 5.5 7.5 128
20DC8P7 1 4 3.0 4 50 9.3 8.7 9.9 13.2 198
20DC011 1 5.5 4 4 50 12.6 11.5 13 17.4 225
20DC015 1 7.5 5.5 4 50 16.8 15.4 17.2 23.1 247
20DC022 1 11 7.5 4 50 24 22 24.2 33 347
20DC030 2 15 11 4 50 33.2 30 33 45 412
20DC037 2 18.5 15 4 50 40.9 37 45 60 460
20DC043 3 22 18.5 4 50 47.5 43 56 74 478
20DC056 3 30 22 4 50 61.9 56 64 86 621
20DC072 3 37 30 4 50 80.5 72 84 112 652
20DC085 4 45 37 4 50 95.1 85 108 144 814
20DH105
(1)
(1) Also applies to “P” voltage class. Fuses must be applied in the (+) leg and (-) leg of the DC Common Bus.
5 55 4 50 120.2 105 116 158 967
45 4 50 95.1 85 128 170 967
20DH125
(1)
5 55 4 50 120.2 125 138 163 891
45 4 50 95.1 96 144 168 891
20DH140 5 75 4 50 159 140 154 210 1263
55 4 50 120.2 105 158 210 1263
20DH170
(1)
6 90 4 50 192 170 187 255 1605
75 4 50 159 140 210 280 1605
20DH205
(1)
6 110 4 40 226 205 220 289 1908
90 4 40 192 170 255 313 1908
20DH260
(1)
6 132 2 40 298 260 286 390 2115
110 2 40 226 205 305 410 2115