Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 65
PowerFlex 700S Drives with Phase II Control
240 Volt AC Input Frames 1…6 Drive Protection Devices
20DB130 5 37 – 141 44.1 175 275 175 500 375 250 – – – –
– 30 113 35.3 125 225 125 400 300 150 – – – –
20DB154 6 45 – 167 60.1 225 350 225 500 500 250 – – – –
– 37 141 50.9 200 300 200 500 450 250 – – – –
20DB192 6 55 – 208 75.0 300 450 300 600 600 400 – – – –
– 45 167 60.1 225 350 225 500 500 250 – – – –
20DB260 6 66 – 255 96.7 300 575 300 750 750 400 – – – –
– 55 199 71.7 225 450 225 600 600 400 – – – –
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings that are shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed
1300% FLA.
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified in this column. Application-specific
thermal considerations may require a larger enclosure.
Drive
Catalog
Number
Frame
HP Rating Input
Ratings
Dual Element
Time Delay Fuse
Non-time Delay
Fuse
Circuit
Breaker
(3)
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Motor
Circuit
Protector
(5)
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings that are shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed
1300% FLA.
140M Motor Starter with Adjustable Current Range
(6)(7)
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
ND HD Amps kVA Min.
(1)
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
Max.
(2)
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Min.
(2
)
Max.
(3)
Max.
(4)
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
Max.
(5)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DB4P2 1 1 0.75 3.3 1.4 5 8 5 15 15 7 M-C2E-B63 M-D8E-
B63
– 7269
20DB6P8 1 2 1.5 5.9 2.4 10 15 10 25 25 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DB9P6 1 3 2 8.3 3.4 12 20 12 35 35 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DB015 1 5 3 13.7 5.7 20 30 20 60 60 30 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DB022 1 7.5 5 19.9 8.3 25 50 25 80 80 30 – M-D8E-C25 M-F8E-C25 7269
20DB028 2 10 7.5 25.7 10.7 35 60 35 100 100 50 – – M-F8E-C32 7269
20DB042 3 15 10 38.5 16.0 50 90 50 150 150 50 – – M-F8E-C45 13630
20DB052 3 20 15 47.7 19.8 60 100 60 200 200 100 – – – –
20DB070 4 25 20 64.2 26.7 90 150 90 275 275 100 – – – –
20DB080 4 30 25 73.2 30.5 100 180 100 300 300 100 – – – –
20DB104 5 40 – 98 40.6 125 225 125 400 300 150 – – – –
– 30 73 30.5 100 175 100 300 300 100 – – – –
20DB130 5 50 – 122 50.7 175 275 175 500 375 250 – – – –
– 40 98 40.6 125 225 125 400 300 150 – – – –
20DB154 6 60 – 145 60.1 200 300 200 600 450 250 – – – –
– 50 122 50.7 175 275 175 500 375 250 – – – –
20DB192 6 75 – 180 74.9 225 400 225 600 575 250 – – – –
– 60 145 60.1 200 300 200 600 450 250 – – – –
20DB260 6 100 – 233 96.8 300 575 300 750 750 400 – – – –
– 75 169 74.9 225 450 225 600 600 400 – – – –
208 Volt AC Input Frames 1…6 Drive Protection Devices (continued)
Drive
Catalog
Number
Frame
kW Rating Input
Ratings
Dual Element
Time Delay Fuse
Non-time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND HD Amp
s
kVA Min.
(1)
Max.
(2)
Min.
(1)
Max.
(2
)
Max.
(4)
Max.
(5)
Available Catalog Numbers
(8)
Minimum Enclosure
Volume (in.
3
)
(9)