66 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
400 Volt AC Input Frames 1…6 Drive Protection Devices
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified in this column. Application-specific
thermal considerations may require a larger enclosure.
Drive
Catalog
Number
Frame
kW Rating Input
Ratings
Dual Element
Time Delay Fuse
Non-time Delay
Fuse
Circuit
Breaker
(5)
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Motor
Circuit
Protector
(7)
(7) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings that are shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed
1300% FLA.
140M Motor Starter with Adjustable Current Range
(8)(9)
(8) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(9) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
ND HD Amps kVA Min.
(3)
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
Max.
(4)
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Min.
(5
)
Max.
(6)
Max.
(6)
(6) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
Max.
(8)
Available Catalog Numbers
(10)
(10) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
Minimum Enclosure
Volume (in.
3
)
(11)
(11) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified in this column. Application-specific
thermal considerations may require a larger enclosure.
20DC2P1 1 0.75 0.55 1.8 1.3 3 6 3 8 15 3 M-C2E-B25 M-D8E-
B25
– 7269
20DC3P5 1 1.5 1.1 3.2 2.2 6 7 6 12 15 7 M-C2E-B40 M-D8E-
B40
– 7269
20DC5P0 1 2.2 1.5 4.6 3.2 6 10 6 20 20 7 M-C2E-B63 M-D8E-
B63
– 7269
20DC8P7 1 4 3.0 7.9 5.5 15 17.5 15 30 30 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DC011 1 5.5 4 10.8 7.5 15 25 15 45 45 15 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DC015 1 7.5 5.5 14.4 10.0 20 30 20 60 60 20 M-C2E-C20 M-D8E-C20 M-F8E-C20 7269
20DC022 1 11 7.5 20.6 14.3 30 45 30 80 80 30 – M-D8E-C25 M-F8E-C25 7269
20DC030 2 15 11 28.4 19.7 35 60 35 120 120 50 – – M-F8E-C32 7269
20DC037 2 18.5 15 35.0 24.3 45 80 45 125 125 50 – – M-F8E-C45 7269
20DC043 3 22 18.5 40.7 28.2 60 90 60 150 150 60 – – – –
20DC056 3 30 22 53 36.7 70 125 70 200 200 100 – – – –
20DC072 3 37 30 68.9 47.8 90 150 90 250 250 100 – – – –
20DC085
(1)
(1) 20DC085 current rating is limited to 45° C ambient.
4 45 – 81.4 56.4 110 200 110 300 300 150 – – – –
– 37 68.9 47.8 90 175 90 275 300 100 – – – –
20DC105 5 55 – 100.5 69.6 125 225 125 400 300 150 – – – –
– 45 81.4 56.4 110 175 110 300 300 150 – – – –
20DC125 5 55 – 121.1 83.9 150 275 150 500 375 250 – – – –
– 45 101 63.7 125 200 125 375 375 150 – – – –
20DC140 5 75 – 135.6 94 200 300 200 400 400 250 – – – –
– 55 121 69.6 150 225 150 300 300 150 – – – –
20DC170 6 90 – 164.6 114 250 375 250 600 500 250 – – – –
– 75 136 94 200 300 200 550 400 250 – – – –
20DC205
(2)
(2) 20DC205 current rating is limited to 40° C ambient.
6 110 – 198.5 138 250 450 250 600 600 400 – – – –
– 90 164 114 250 375 250 600 500 250 – – – –
20DC260 6 132 – 254.7 166 350 550 350 750 750 400 – – – –
– 110 199 138 250 450 250 600 600 400 – – – –