68 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
480 Volt AC Input Frames 1…6 Drive Protection Devices
Drive
Catalog
Number
Frame
HP Rating Input Ratings Dual Element
Time Delay Fuse
Non-time Delay
Fuse
Circuit
Breaker
(3)
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Motor
Circuit
Protector
(5)
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings that are shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
140M Motor Starter with Adjustable Current Range
(6)(7)
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
ND HD Amps kVA Min.
(1)
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
Max.
(2)
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Min.
(3)
Max.
(4
)
Max.
(4)
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
Max.
(6)
Available Catalog Numbers
(8)
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
Minimum Enclosure
Volume (in.
3
)
(9)
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified in this column. Application-specific thermal considerations may require a
larger enclosure.
20DD2P1 1 1 0.7
5
1.6 1.4 3 6 3 8 15 3 M-C2E-B25 7269
20DD3P4 1 2 1.5 2.6 2.2 4 8 4 12 15 7 M-C2E-B40 M-D8E-B40 7269
20DD5P0 1 3 2 3.9 3.2 6 10 6 20 20 7 M-C2E-B63 M-D8E-B63 7269
20DD8P0 1 5 3 6.9 5.7 10 15 10 30 30 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DD011 1 7.5 5 9.5 7.9 15 20 15 40 40 15 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DD014 1 10 7.5 12.5 10.4 17.5 30 17.5 50 50 20 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DD022 1 15 10 19.9 16.6 25 50 25 80 80 30 M-D8E-C25 M-F8E-C25 7269
20DD027 2 20 15 24.8 20.6 35 60 35 100 100 50 M-F8E-C32 7269
20DD034 2 25 20 31.2 25.9 40 70 40 125 125 50 M-F8E-C45 7269
20DD040 3 30 25 36.7 30.5 50 90 50 150 150 50 M-F8E-C45 13630
20DD052 3 40 30 47.7 39.7 60 110 60 200 200 70
20DD065 3 50 40 59.6 49.6 80 125 80 250 250 100
20DD077 4 60 72.3 60.1 100 170 100 300 300 100
50 59.6 49.6 80 125 80 250 250 100
20DD096 5 75 90.1 74.9 125 200 125 350 350 125
60 72.3 60.1 100 170 100 300 300 100
20DD125 5 100 117 97.6 150 250 150 500 375 150
75 90.1 74.9 125 200 125 350 350 125
20DD156 6 125 146.5 121.7 200 350 200 600 450 250
–10
0
131 97.6 175 250 175 500 375 250
20DD180 6 150 169 140.5 225 400 225 600 500 250
12
5
147 121.7 200 350 200 600 450 250
20DD248 6 200 232.8 188 300 550 300 700 700 400
15
0
169 140.5 225 400 225 600 500 250