Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 69
PowerFlex 700S Drives with Phase II Control
480 Volt AC Input Frames 9…13 Drive Protection Devices
Drive Catalog
Number
Frame
HP Rating Input
Ratings
Dual Element Time Delay Fuse Non-time Delay Fuse Bussmann Style Semi-
conductor Fuse
Circuit
Breaker
(4)
(4) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Motor Circuit
Protector
(6)
(6) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings that are shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed
1300% FLA.
ND HD Amps Min.
(1)
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
Max.
(3)
(3) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
Min.
(1)
Max.
(3)
Max.
(5)
(5) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
Max.
(5)
20DD261 9 200 - 252 350 550 350 700 170M5813 700 400
- 150 207 275 450 275 600 170M5813 600 300
20DD300 9 250 - 290 400 650 400 900 170M5813 900 400
- 200 247 350 550 350 700 170M5813 700 400
20DD385 10 300 - 372 500 850 500 1100 170M5813 1100 600
- 250 302 400 650 400 900 170M5813 900 400
20DD460 10 350 - 444 600 1000 600 1300 170M8547 1300 600
- 300 388 500 850 500 1100 170M8547 1100 600
20DD500 10 450 - 483 650 1000 650 1500 170M8547 1500 700
- 350 423 550 900 550 1200 170M8547 1200 600
20DD590 11 500 - 570 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
- 450 524 700 (1 per phs)
350 (2 per phs)
1100 700 (1 per phs)
350 (2 per phs)
1500 170M5813 1500 700
20DD650 11 500 - 628 800 (1 per phs)
400 (2 per phs)
1400 800 (1 per phs)
400 (2 per phs)
1900 170M5813 1900 800
- 500 594 750 (1 per phs)
375 (2 per phs)
1300 750 (1 per phs)
375 (2 per phs)
1700 170M5813 1700 800
20DD730 11 600 - 705 900 (1 per phs)
450 (2 per phs)
1600 900 (1 per phs)
450 (2 per phs)
2100 170M5813 2100 900
- 500 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20DD820 12 700 - 792 1000 (1 per phs)
500 (2 per phs)
1800 1000 (1 per phs)
500 (2 per phs)
2400 170M8547 2400 1000
- 600 735 900 (1 per phs)
475 (2 per phs)
1600 900 (1 per phs)
475 (2 per phs)
2100 170M8547 2100 1000
20DD920 12 800 - 888 1200 (1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M8547 2700 1200
- 700 826 1100 (1 per phs)
550 (2 per phs)
1800 1100 (1 per phs)
550 (2 per phs)
2400 170M8547 2400 1200
20DD1K0 12 900 - 994 1300 (1 per phs)
650 (2 per phs)
2300 1300 (1 per phs)
650 (2 per phs)
3000 170M8547 3000 1300
- 800 927 1200 (1 per phs)
600 (2 per phs)
2000 1200 (1 per phs)
600 (2 per phs)
2700 170M8547 2700 1200
20DD1K1 13 1000 - 1110 1400 (1 per phs)
700 (2 per phs)
(2)
(2) Fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
2500
(2)
1400 (1 per phs)
700 (2 per phs)
(2)
3400
(2)
170M6466
(2)
3400 1400
- 900 994 1300 (1 per phs)
650 (2 per phs)
(2)
2300 (2) 1300 (1 per phs)
650 (2 per phs)
(2)
3000
(2)
170M6466
(2)
3000 1300
20DD1K3 13 1200 - 1255 1600 (1 per phs)
800 (2 per phs)
(2)
2900 (2) 1600 (1 per phs)
800 (2 per phs)
(2)
3900
(2)
170M6466
(2)
3900 1600
- 1000 1110 1400 (1 per phs)
700 (2 per phs)
(2)
2500 (2) 1400 (1 per phs)
700 (2 per phs)
(2)
3400
(2)
170M6466
(2)
3400 1400
20DD1K4 13 1250 - 1400 1800 (1 per phs)
900 (2 per phs)
(2)
3200 (2) 1800 (1 per phs)
900 (2 per phs)
(2)
4300
(2)
170M6466
(2)
4300 1800
- 1000 1158 1500 (1 per phs)
750 (2 per phs)
(2)
2700 (2) 1500 (1 per phs)
750 (2 per phs)
(2)
3600
(2)
170M6466
(2)
3600 1500