Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 77
PowerFlex 700S Drives with Phase II Control
810 Volt DC Input Frames 9…14 Drive Protection Devices
932 Volt DC Input Frames 5 & 6 Drive Protection Devices
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30A to 400 A; Bulletin No. 194, 30 A to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Bussmann Type JKS, all sizes; Type 170M, Case
Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.
Drive Catalog Number Frame HP Rating DC Input Ratings Fuse Bussmann Style Fuse
ND HD Amps
20DK170 9 150 – 192 400 170M5608
– 150 162 400 170M5608
20DK208 9 200 – 235 450 170M5609
– 150 192 450 170M5609
20DK261 10 250 – 294 450 170M5609
– 200 235 450 170M5609
20DK325 10 350 – 367 550 170M6609
– 250 294 550 170M6609
20DK385 10 400 – 434 700 170M6611
– 350 367 700 170M6611
20DK416 10 450 – 469 800 170M6612
– 350 367 800 170M6612
20DK460 11 500 – 519 450 (2 per phs) 170M5609
– 400 434 450 (2 per phs) 170M5609
20DK502 11 500 – 566 500 (2 per phs) 170M6608
– 500 519 500 (2 per phs) 170M6608
20DK590 11 600 – 666 500 (2 per phs) 170M6608
– 500 566 500 (2 per phs) 170M6608
20DK650 12 700 – 733 500 (2 per phs) 170M6608
– 650 666 500 (2 per phs) 170M6608
20DK750 12 800 – 846 630 (2 per phs) 170M6610
– 700 733 630 (2 per phs) 170M6610
20DK820
(1)
(1) 20DK820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
12 900 – 925 630 (2 per phs) 170M6610
– 700 733 630 (2 per phs) 170M6610
20DK920 13 1000 – 1038 2400 170M7107
– 900 925 2400 170M7107
20DK1K0 13 1100 – 1162 2400 170M7107
– 1000 1038 2400 170M7107
20DK1K1 13 1300 – 1331 2400 170M7107
– 1100 1162 2400 170M7107
20DK1K5 14 1600 – 1692 – 170M8610
– 1400 1467 – 170M8610
Drive Catalog Number Frame kW Rating DC Input Ratings Fuse Non-time Delay Fuse
(1)
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30A to 400 A; Bulletin No. 194, 30A to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Bussmann Type JKS, all sizes; Type 170M, Case Sizes
1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please contact the factory.
ND HD Amps
20DW098 5 90 – 92.3 160 HSJ160
– 75 92.3 160 HSJ160
20DW142 6 132 – 162.2 250 HSJ250
– 110 134.9 250 HSJ250