78 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
932 Volt DC Input Frames 9…14 Drive Protection Devices
Drive Catalog Number Frame kW Rating DC Input Ratings Fuse Bussmann Style Fuse
ND HD Amps
20DM170 9 160 – 200 315 170M3746
– 132 170 315 170M3746
20DM208 9 200 – 245 400 170M5742
– 160 200 400 170M5742
20DM261 10 250 – 307 500 170M5744
– 200 245 500 170M5744
20DM325 10 315 – 383 630 170M5746
– 250 307 630 170M5746
20DM385 10 355 – 453 700 170M6745
– 315 383 700 170M6745
20DM416 10 400 – 490 700 170M6745
– 315 383 700 170M6745
20DM460 11 450 – 542 450 (2 per phs) 170M5743
– 355 453 450 (2 per phs) 170M5743
20DM502 11 500 – 591 500 (2 per phs) 170M5744
– 400 542 500 (2 per phs) 170M5744
20DM590 11 560 – 695 500 (2 per phs) 170M5744
– 500 591 500 (2 per phs) 170M5744
20DM650 12 630 – 765 550 (2 per phs) 170M5745
– 560 695 550 (2 per phs) 170M5745
20DM750 12 710 – 883 630 (2 per phs) 170M5746
– 630 765 630 (2 per phs) 170M5746
20DM820
(1)
(1) 20DM820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
12 800 – 965 630 (2 per phs) 170M5746
– 630 765 630 (2 per phs) 170M5746
20DM920 13 900 – 1038 2400 170M7107
– 800 925 2400 170M7107
20DM1K0 13 1000 – 1162 2400 170M7107
– 900 1038 2400 170M7107
20DM1K1 13 1100 – 1331 2400 170M7107
– 1000 1162 2400 170M7107
20DM1K5 14 1500 – 1766 – 170M8610
– 1300 1530 – 170M8610