Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 79
PowerFlex 700S Drives with Phase II Control
Drive Mounting Clearances and Dimensions
Minimum Mounting Clearances
Adhesive Label
With Adhesive
Label Removed
With Adhesive Label
Left in Place
50.8 mm
(2.0 in.)
101.6 mm (4.0 in.)
Air ow through the drive
must not be impeded.
101.6 mm (4.0 in.)
101.6 mm (4.0 in.)
101.6 mm (4.0 in.)
101.6 mm (4.0 in.)
101.6 mm (4.0 in.)
Frames 1…6
Specified vertical clearance requirements are intended to be from the drive to the closest object that can restrict airflow through the drive
heat sink and chassis. The drive must be mounted in a vertical orientation as shown, and must make full contact with the mounting
surface. Do not use standoffs or spacers. In addition, inlet air temperature must not exceed the product specification.
Note: Refer to the “Drive Fuse and Circuit Breaker Ratings” tables beginning on page
64 for information on drive ambient operating
temperatures.
400.0 mm
(15.75 in.)
80.0 mm
(3.2 in.)
50.0 mm
(1.97 in.)
350.0 mm
(13.8 in.)
400.0 mm
(15.75 in.)
350.0 mm
(13.8 in.)
50.0 mm
(1.97 in.)
Frame 9