50 Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Table 30 - 0…20 mA Analog Input - Unipolar Speed Reference at Terminals Ai1±
22-Series I/O Module TB1
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 4 (or port where y
our 22-Series I/O Module is installed), See page 10: P60 [Anlg In1 Value]
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P61 [Anlg In1 Hi] = 20 mA
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P62 [Anlg In1 Lo] = 0 mA
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P60 [Anlg In1 Value]
Port 0: P592 [Selected Spd Ref]
Jumpers set to current mode.
Table 31 - 0…+10V Analog Input - Unipolar Speed Reference at Terminals Ai1±
22-Series I/O Module TB1
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 4, (or port where y
our 22-Series I/O Module is installed)See page 10: P60 [Anlg In1 Value]
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P61 [Anlg In1 Hi] = 10 Volt
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P62 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P60 [Anlg In1 Value]
Port 0: P592 [Selected Spd Ref]
Jumpers set to voltage mode.
Table 32 - 10k Ohm Potentiometer - Unipolar Speed Reference at Terminals Ai1±
22-Series I/O Module TB1
Set Direction Mode
Port 0: P308 [Direction Mode] =
0 “Unipolar”
Set Selection
Port 0: P545 [Spd Ref A Sel] = Port 4 (or port where
your 22-Series I/O Module is installed), See page 10: P60 [Anlg In1 Value]
Adjust Scaling
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P61 [Anlg In1 Hi] = 10 Volt
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P62 [Anlg In1 Lo] = 0 Volt
Port 0: P547 [Spd Ref A AnlgHi] = 60 Hz
Port 0: P548 [Spd Ref A AnlgLo] = 0 Hz
View Results
Port 4 (or port where your 22-Series I/O Module is installed), See page
10: P60 [Anlg In1 Value]
Port 0: P592 [Selected Spd Ref]
Jumpers set to voltage mode.
Ai1–
Ai1+
+
Common
Ai0
Ai1
Ai1–
Ai1+
+
Common
Ai0
Ai1
10VC
+10V
Ai1–
Ai1+
Ai0
Ai1