70 Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Direction Mode
Table 45 - 753 Main Control Board TB1 2-Wire Control with Reversing Wiring
2-Wire Control Reversing
Internal 24V Supply
753 Main Control Board TB1
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Set Selection
Port 0: P164 [DI Run Forward] = Port 0: P220 [Digital In Sts], bit 1 = Digital In 1
Port 0: P165 [DI Run Reverse] = Port 0: P220 [Digital In Sts], bit 2 = Digital In 2
View Results
Port 0: P220 [Digital In Sts]
Port 0: P935 [Drive Status 1]
2-Wire Control Reversing
External 24V Supply
753 Main Control Board TB1
Run Fwd
Run Rev
Di C
Di 1
Di 2
+24V
Run Fwd
Run Rev
Common
Table 46 - 750-Series I/O Module TB1 2-Wire Control with Reversing Wiring
2-Wire Control Reversing
External 24V Supply
20-750-2262C-2R
20-750-2263C-1R2T
750-Series I/O Module TB1
Set Direction Mode
Port 0: P308 [Direction Mode] = 0 “Unipolar”
Configuration
Port 0: P150 [Digital In Cfg], = 1 “Run Level”
Set Selection
Port 0: P164 [DI Run Forward] = Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts],
b
it 0 = Input 0
Port 0: P165 [DI Run Reverse] = Port 4 (or port where
y
our I/O Module is installed): P1 [Dig In Sts],
bit 1 = Input 1
View Results
Port 4 (or port where your I/O Module is installed): P1 [Dig In Sts]
Port 0: P935 [Drive Status 1]
Di C
Di 0
Di 1
+24V
Run Fwd
Run Rev
Common