Rockwell Automation Publication 750-QS001A-EN-P - March 2015 61
Reference Section
7. If required, set the value of parameters 15 [Gateway Cfg 1] through 18 [Gateway Cfg 4] to the desired value for the
gateway device.
8. Reset the option module. See Reset the Option Module on page 62.
Default = 0.0.0.0 255.255.255.255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Edit Gateway Cfg 1
0
0 << 255
ESC
ENTER
Stopped
0.000 Hz
AUTO
F
Table 39 - PowerFlex 750-Series 20-750-ENETR Option Module Parameter Settings
No. Drive
Parameter
Name
User
Setting
Default Value/Options Notes
2 Port Number 5 0 4, 5, or 6 Port Number
5 Net Addr Sel 13 3 1 = Parameters
2 = BOOTP
3 = DHCP
7 IP Addr Cfg 1 192 Example IP Address.
8 IP Addr Cfg 2 168 0
9 IP Addr Cfg 3 1
10 IP Addr Cfg 4 xxx Set to desired value.
11 Subnet Cfg 1 255
12 Subnet Cfg 2 255
13 Subnet Cfg 3 255
14 Subnet Cfg 4 0
Leave the remainder of the Embedded EtherNet/IP (P
ort 13) parameters at their default settings.