Publication 2711-UM014B-EN-P
B-4 Messages, Codes and Self-Test Numbers
394 File not supported Reminder/File
Transfer Status
File is incompatible with the terminal’s
firmware.
In PanelBuilder32, click the Catalog &
Revisions button on the Setup tab on the
Application Settings dialog. Select a
firmware version that matches your
terminal.
395 File not supported Reminder/File
Transfer Status
File is incompatible with the operator
input type (keypad, touch or keypad and
touch) of terminal.
In PanelBuilder32, select the Setup tab on
the Application Settings dialog. Select
the type of operator input that matches
your terminal.
396 File not supported Reminder/File
Transfer Status
File is incompatible with the terminal. Download the file to the terminal again. If
problem reoccurs, contact technical
support.
415 Retained memory
lost.
Presets were
loaded.
Reminder The battery backed memory was invalid
during startup. The system defaulted to
preset values instead of the last states.
No action necessary. Terminal reverts to
defaults.
436 Logic Controller has
screen control
Reminder You tried to change the application screen
but it is configured for controller only
access.
No action required, controller will change
screens as programmed.
634 Read Fail or
Write Fail
Status ControlLogix Tag or address does not exist
or is the wrong data type.
Designated slot does not contain a
ControlLogix Processor.
Check tag address.
Check for data type mismatch.
Verify ControlLogix slot location.
1109 Font file
unavailable,
Font error = ****
Minor Fault or
Terminal Fault
You downloaded an application to the
PanelView without the appropriate
memory card (containing the font file)
inserted in the card slot of the terminal.
From the Memory Card screen, press the
Disconnect button to close the files on the
card. Remove the card from the card slot.
Locate the card containing the font file or
copy the correct font file to a card. Insert
the correct memory card in the card slot
and enter Run mode.
1110 No valid
application
Reminder You tried to run an application that has
not been downloaded to the terminal.
Download application to terminal.
1118 Access denied. Status Wrong password entered. Enter a valid password.
1119 Access denied. Status Password not recognized Enter a valid password.
1120 Security tampering. Status PVA file was corrupted - attempt to
bypass security was detected
New application file must be downloaded
to the terminal.
1121 No operator
selected.
Status There is no currently selected operator,
but a password change has been
requested
Select the operator requiring the new
password.
1122 Password change is
not allowed.
Reminder Password is unchangeable Password cannot be changed at the
current level of security.
1123 Password change is
not allowed.
Reminder Operator cannot change password Current operator does not have access for
password changes.
1124 New password
must be entered
before it can be
verified.
Reminder New pass words must be entered twice. Enter the new password again to verify
that it was entered correctly.
1125 New and verify
passwords differ.
Status The same password was not entered for
verification.
Enter the same password for New and
Verify.
1126 Please verify new
password.
Reminder New pass words must be entered twice. Enter the new password again.
1127 Password changed Reminder Password change is effective. You must use new password for security
access.
Error Number Terminal
Messages
Type Meaning Recommended Action