Publication 2711-UM014B-EN-P
B-6 Messages, Codes and Self-Test Numbers
ControlNet Terminal Messages
See Terminal Codes for messages below
Error Number Terminal
Messages
Type Meaning Recommended Action
634 PanelView offline Comm Warning PanelView is offline. Check connections
634 Write fail. Comm Warning PanelView is communicating with the
controller. The data table address does
not exist.
Check / define data table address in the
controller.
634 Write timeout. Comm Warning PanelView is not communicating with the
logic controller.
Check connections and node
configuration in the application.
634 Read fail. Comm Warning PanelView is communicating with the
controller. The data table address does
not exist.
Check/define data table address in the
controller.
634 Read timeout. Comm Warning PanelView is not communicating with the
controller.
Check/define data table address in the
controller.
636 Initial write failed. Reminder Write to Logic Controller on Startup was
configured and on powerup, the
PanelView could not write initial values to
a nodes data table address.
or
Write to Logic Controller on Startup was
not configured and the PanelView was
unable to write a controller. Note: The
error is only displayed on the first write
attempt.
Check/define data table address in the
controller.
Check communication connections and
node configuration in the application.