60 Rockwell Automation Publication 42EF-UM001A-EN-P - September 2015
Device Parameters
Process Data
Parameter Name Sub-Index Access Default Allowable Values Data Type (Length)
Tri gge red Depends on mode RO 0 = Not Triggered
0 = Not Triggered
1 = Triggered
BooleanT
bitLength=32
bitOffset=0
MarginLowAlarm Depends on mode RO 0 = Off
0 = Off
1 = On
BooleanT
bitLength=32
bitOffset=1
ProximityAlarm Depends on mode RO 0 = Off
0 = Off
1 = On
BooleanT
bitLength=32
bitOffset=2
Gain Depends on mode RO n/a 0 to 255
UIntegerT
bitLength=8
bitOffset=8
Contrast Depends on mode RO n/a 0 to 255
UIntegerT
bitLength=8
bitOffset=16
TemperatureInternal Depends on mode RO n/a -40 to 125
BooleanT
bitLength=32
bitOffset=24
DurationTriggered Depends on mode RO n/a 0 to 4095
UIntegerT
bitLength=12
bitOffset=20
DurationNotTriggered Depends on mode RO n/a 0 to 4095
BooleanT
bitLength=32
bitOffset=8
SignalStrength Depends on mode RO n/a 0 to 65535
UIntegerT
bitLength=16
bitOffset=16
Count Depends on mode RO n/a 0 to 65535
UIntegerT
bitLength=16
bitOffset=16
Process D
a
ta parameter allows a maximum of four bytes.