507404-02Page 10 of 80 Issue 1448
WARNING
Improper installation of the furnace can result in
personal injury or death. Combustion and ue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace
should be sealed airtight to the return air plenum. A
door must never be used as a portion of the return air
duct system. The base must provide a stable support
and an airtight seal to the furnace. Allow absolutely no
sagging, cracks, gaps, etc.
For no reason should return and supply air duct systems
ever be connected to or from other heating devices such
as a replace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property
damage could result.
Return Air Guidlines
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
Furnace applications which include side return air and a
condensate trap installed on the same side of the cabinet
(trap can be installed remotely within 5 ft.) require either a
return air base or eld-fabricated transition to accommodate
an optional IAQ accessory taller than 14.5”. See Figure 13.
Figure 12
Installation Clearances
* Front clearance in alcove installation must be 24 in. (610 mm). Main-
tain a minimum of 24 in. (610 mm) for front service access.
Allow proper clearances to accommodate condensate trap and vent
pipe installation.
For installations on a combustible oor, do not install the furnace
directly on carpeting, tile or other combustible materials other than
wood ooring.
Figure 13
Side Return Air
(with transition and lter)