507404-02Page 36 of 80 Issue 1448
Condensate line must slope downward away from the trap
to drain. If drain level is above condensate trap, condensate
pump must be used. Condensate drain line should be routed
within the conditioned space to avoid freezing of condensate
and blockage of drain line. If this is not possible, a heat
cable kit may be used on the condensate trap and line.
Heating cable kit is available in various lengths; 6 ft. (1.8
m) - kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69; and 50 ft.
(15.2 m) - kit no. 26K70.
Do not use copper tubing or existing copper condensate
lines for drain line.
CAUTION
Figure 50
CONDENSATE TRAP LOCATIONS
(Unit shown in upow position with remote trap)
*Piping from furnace must slope down a minimum of 1/4”
per ft. toward trap.
Figure 52
UNIT WITH EVAPORATOR COIL
CONDENSATE TRAP LOCATIONS
(Unit shown in horizontal right hand discharge position)
Figure 51
*Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.