43We reserve the right to make technical changes | 83055600dUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Parameter Factory setting
Adjustment during
commissioning *)
Value range (adjustable steps) Access
Output heat. max. 100 % 50 % – 100 % (↕1) Fitter
Control dhw Auto Auto • Manual Fitter
output dhw. 100 % 1 % – 100 % (↕1) Fitter
output dhw max 100 % 50 % – 100 % (↕1) Fitter
output cooling 100 % 1 % – 100 % (↕1) Fitter
dT cooling 5 K 1 K – 5 K (↕0.1) Fitter
Set bypass valve No No • Yes User
Second heat generator
Second heat gen. 1
Type No No • El.Rod • Boiler • Thermal Fitter
Function HW a SW No • HW a SW • Heating Fitter
Position Integrated – – – • Integrated • Tank Fitter
Outlet installation-dependent – – – • (output contact) Fitter
Second heat gen. 2
Type No No • El.Rod Fitter
Function No No • Heating • SW Fitter
Position – – – – – – • Tank Fitter
Outlet – – – – – – • (output contact) Fitter
Pump ow
Pump ow ZUP 60 s 0 – 60 s (↕5) Fitter
Smart
Smart Home ID – 1 – 4 (↕1) User
Heating circuit No No • Yes User
range + 0 K 0 K – 5 K (↕1) User
range – 0 K 0 K – 5 K (↕1) User
mixing circ 1 No No • Yes User
range + 0 K 0 K – 5 K (↕1) User
range – 0 K 0 K – 5 K (↕1) User
DHW No No • Yes User
intelligent defrost No No • Yes Fitter
Smart Grid
Decrease Heating -2 K -0.5 K – -25 K (↕0.5) Fitter
Increase heating 2 K 0.5 K – 5 K (↕0.5) Fitter
Increase SW 2 K 0.5 K – 10 K (↕0.5) Fitter
*) Please enter the adjusted values. If 2 heat pumps are connected, enter both values. Mark not applicable with — .