EasyManua.ls Logo

Amana 2246008 - User Manual

Amana 2246008
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Terminals S1 and S2 can be used for an indoor remote sensor.
The indoor remote sensor is used to read the indoor temperature
in a different location. This is benecial when the thermostat is not
mounted in the ideal location.
1. Remove cover from remote sensor housing.
2. Select an appropriate location for mounting the remote sensor.
3. Mount remote sensor unit using hardware provided.
4. Install two strand shielded wire between remote sensor and
thermostat. Shielded wire is recommended.
Do not run remote sensor wire in conduit with other wires.
Wire 1 should run between the S1 terminal on the thermostat
and the S1 terminal on the remote sensor
Wire 2 should run between the S2 terminal on the thermostat
and the S2 terminal on the remote sensor
Connect the shielding of the wire to the S2 terminal on the thermostat
5. Congure the thermostat to operate with the remote indoor sensor (see Conguration Mode setting 13).
Remote Sensor Installation (Optional)
Note: Remoteoroutdoorsensorreadingcanbe
displayedbysimultaneouslypressingthe
DownandSYSbuttons.
Remote Sensor:
(Shown:OptionalICMACC-RT103RemoteIndoor
Sensor;foroutdoorsensor,orderACC-OD103.)
Specifications
Electrical rating: 24 VAC (18-30 VAC)
1 amp maximum per terminal
3 amp maximum total load
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System congurations: 2-stage heat, 2-stage cool, heat pump, gas, oil, electric
Timing: Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode for 5 seconds)
Backlight Operation: 10 seconds
Terminations: S1, S2, R, C, W/O/B, Y1, W2, Y2, G
Package Contents/Tools Required
Package includes: Amana
®
2246008 thermostat on base, thermostat cover, wiring labels, screws and wall
anchors, Installation, Operation and Application Guide
Tools required for installation: Drill with 3/16” bit, hammer, screwdriver
Important Safety Information
WARNING!
:
Always turn off power at the main power supply before installing, cleaning, or removing
thermostat.
This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC
Do not short across terminals of gas valve or system control to test operation; this will damage your thermostat
and void your warranty
All wiring must conform to local and national electrical and building codes
Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage your A/C system
and cause personal injuries
Use this thermostat only as described in this manual
To Remove Existing Thermostat
ELECTRICAL SHOCK HAZARD
– Turn off power at the main service panel by removing the fuse
or switching the appropriate circuit breaker to the OFF position before removing the existing
thermostat.
1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circuit
breaker off.
2. Remove cover of old thermostat. This should expose the wires.
3. Label the existing wires with the enclosed wire labels before removing wires.
4. After labeling wires, remove wires from wire terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how to install this thermostat.
To Install Thermostat
ELECTRICAL SHOCK HAZARD
– Turn off power at the main service panel by removing the fuse
or switching the appropriate circuit breaker to the OFF position before removing the existing
thermostat.
IMPORTANT: Thermostatinstallationmustconformtolocalandnationalbuildingandelectricalcodesand
ordinances.
Note: Mountthethermostataboutvefeetabovetheoor.Donotmountthethermostatonanoutsidewall,in
directsunlight,behindadoor,orinanareaaffectedbyaventorduct.
1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circuit breaker
off.
2. To remove cover, pull gently at the seam at the top.
3. Put thermostat base against the wall where you plan to mount it (Be sure wires will feed through the wire opening
in the base of the thermostat).
4. Mark the placement of the mounting holes.
5. Set thermostat base and cover away from working area.
6. Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
7. Use a hammer to tap supplied anchors in mounting holes.
8. Align thermostat base with mounting holes and feed the control wires through slit in thermal intrusion barrier and
into wire opening.
9. Use supplied screws to mount thermostat base to wall.
10. Insert stripped, labeled wires in matching wire terminals.
CAUTION!
: Besureexposedportionofwiresdoesnottouchotherwires.
11. Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper
terminal.
12. Turn on power to the system at the main service panel.
13. Congure thermostat to match the type of system you have.
14. Replace cover on thermostat by snapping it in place.
15. Test thermostat operation as described in “Testing the Thermostat”.
Parts Diagram
Conguration
switch
Reset switch
Left (system) button
Right (fan) button
Down button
Up button
Icon Descriptions
Cooling operation icon
Fan operation icon
Heating operation icon
Lock mode activated
Room temperature
offset activated
S1 S2 R C W
O/B
GY1 W2 Y2
RESET CONFIG
Terminal Designator Descriptions
1
ST
Cool 2
ND
Cool 1
ST
Heat 2
ND
Heat
Heat/Cool Y1,G YI,Y2,G W1,G* W1,W2,G*
Heat Pump (One Compressor) Y1,G,O Y1,G,O Y1,G,B Y1,W2,G,B
Heat Pump (Two Compressors) Y1,G,O Y1,Y2,G,O Y1,G,B Y1,Y2,G,B
Electric Heat (Heat Pump Only) N/A N/A W2,G W2,G
* G not energized when congured as a gas/oil system
The Amana
®
2246008 thermostat is congurable for all systems. The conguration directly affects the outputs.
Use the output chart to correctly congure and wire the thermostat to your system.
Amana® 2246008 Output Chart
Configuration Mode
OFF
PM
1. Verify the Amana
®
2246008 is in the OFF mode.
Press the SYS (left) button until off mode displays.
2. Remove the cover of the thermostat by gently pulling near one of the corners at
the top of the thermostat.
3. Press the CONFIG button for 1 second while the Amana
®
2246008 is in OFF
mode.
To exit conguration mode, press the CONFIG switch for 1 second.
Press the up or down button to change settings within each screen.
Down button
Up button
Press the right button to advance to the next screen.
Note: Pressingthe
left
buttonwillreturnyoutothepreviousscreen.
Left
button
Right
button
The conguration mode is used to set the Amana
®
2246008 to match your heating/cooling system. The Amana
®
2246008 functions with heat pump, air conditioning, gas, oil or electric heat systems.
To congure the Amana
®
2246008, perform the following steps:
CONFIG
S1 S2 R C W
O/B
GY1W2 W3Y2
RESET CONFIG
FP
R 24 VAC hot
C 24 VAC common
W1/O/B – Congurable
W1 – 1st stage heat for non-heat pump systems
O – cool active reversing valve
B – heat active reversing valve
Y1 1st stage cool, 1st stage heat for heat pumps
W2 2nd stage heat for non-heat pump systems, Electric Heat for heat pump systems
Y2 2nd stage cool for 2 compressor systems, 2nd stage heat for 2 compressor heat pump systems
G Fan
Configuration Mode Settings
The setup screens for Conguration Mode are as follows:
1. Temperature Scale (F or C)
Choose Fahrenheit or Celsius.
Press the up or down button to select.
Press the
right
button to advance to the next screen.
2. 1
st
Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between your “setpoint” temperature and your “turn on”
temperature.
Press the up or down button to set differential value.
Press the right button to advance to the next screen.
4. Staged Off Outputs
Select whether the outputs for heating and cooling are staged off independently or
are satised simultaneously.
1 = outputs staged off independently
0 = outputs off simultaneously
Press the up or down button to set.
Press the right button to advance to the next screen.
5. Minimum Deadband (1°F to 9°F) (1°C to 5°C)
Set the minimum separation between heat setpoint and cool setpoint in Auto
Changeover Mode.
Press the up or down button to set deadband value.
Press the right button to advance to the next screen.
7. Auxiliary Delay ON – (0-30 minutes) – Set the delay time in minutes for auxiliary heat
to be locked out after a call for second stage. This extra savings feature is used to
temporarily lock out auxiliary heat devices, allowing just heat pump to try to satisfy heat
call.
Press the up or down button to select.
Press the right button to advance to the next screen.
8. Lockout (0-8°, NITE, COOL-HEAT) – Select the number of degrees set temperature
can be changed during keypad lockout or select to lockout during NITE period only.
COOL-HEAT lockout allows adjustment of the set temperatures to the maximum heat
set temperature selected in Step 9 and minimum cool set temperature selected in
Step 10.
Note: Themodecannotbechangedwhenthethermostatislocked.
Press the up or down button to select.
Press the right button to advance to the next screen.
9. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.
10. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.
13. Temperature Sensor (1-4)
1. Only on-board sensor determines room temperature.
2. Only remote sensor determines room temperature.
3. Average temperature of on-board and remote sensor.
4. Only on-board sensor will be used until NITE period, and then only
remote sensor is used.
Note: Ifthereisnoremotesensor,option1mustbeselected.
Press the up or down button to select.
Press the right button to advance to the next screen.
12. Maximum Cycles Allowed Per Hour (- -, 2-6)
- - = as many as needed, 2-6 = maximum cycles/hour
Press the up or down button to select.
Press the right button to advance to the next screen.
11. Room Temperature Offset (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Note: Whennotsetto0, willdisplay.
Press the up or down button to select.
Press the right button to advance to the next screen.
3. 2
nd
Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between when stage 1 turns on and when stage 2 turns on.
Press the up or down button to set differential value.
Press the right button to advance to the next screen.
6. System – Set for heat pump, non-heat pump, reversing valve operation and number of compressors in your
system.
Press the up or down button to select.
Press the right button to advance to the next screen.
Choose System
Reversing Valve
Active
Number of Compressors
or Compressor Stages
Type of
Heat
Heat Pump
HP O 1
HP b 1
HP O 2
HP b 2
Non-Heat
Pump
Heat Gas
Heat Electric
OFF
14. Cooling Fan Delay Off Time (0, 30, 60, 90 seconds)
Select the fan purge time for cooling.
Press the up or down button to select.
Press the right button to advance to the next screen.
Wiring Diagrams
120
VAC
24 VAC
Heat #1
Cool #1
Heat #2
Cool #2
Fan
Transformer
Heat/Cool Systems
Optional
remote or
outdoor sensor
* outdoor sensor only reads outdoor temperature
120
VAC
24 VAC
Reversing Valve
Fan
Compressor
Auxiliary Heat #1
Single Compressor
heat pump with electric backup
Dual Compressor
heat pump with electric backup
120
VAC
24 VAC
Reversing Valve
Compressor #1
Electric Heat
Fan
Compressor #2
Transformer
Optional
remote or
outdoor sensor
Transformer
Optional
remote or
outdoor sensor
* outdoor sensor only reads outdoor temperature
7-Day, 5-2-Day or 5-1-1-Day Programmable
Congurable
2-Stage Heat/2-Stage Cool Systems
2-Stage Heat Pump Systems
Large Display With Backlight
Selectable Fahrenheit or Celsius
Compatible with Gas, Oil, or Electric
Relay Outputs
(minimum voltage drop in thermostat)
Remote Sensor Compatible
Ideally Suited for:
Residential (New Construction/Replacement)
Light Commercial
Installation, Operation &
Application Guide
www.amana-ptac.com
2246008
Programmable Electronic Thermostat
2 Heat/2 Cool, Auto Changeover, Hardwire
Press the CONFIG button for 2 seconds to exit conguration.
Question and Answer IconNeed help?

Do you have a question about the Amana 2246008 and is the answer not in the manual?

Summary

Thermostat Installation and Operation Guide

Removing Existing Thermostat

Step-by-step instructions for safely removing the old thermostat from the wall.

Installing the Thermostat

Detailed procedures for mounting and wiring the new thermostat correctly.

Terminal Designator Explanations

Explanation of the function for each terminal on the thermostat's wiring base.

Important Safety Precautions

Critical safety warnings and handling instructions for the thermostat.

Thermostat Testing and Settings

Configuration Mode Settings

How to access and adjust advanced configuration settings for system compatibility.

Troubleshooting

Troubleshooting Common Issues

Guidance on diagnosing and resolving common problems with the thermostat.

Summary

Thermostat Installation and Operation Guide

Removing Existing Thermostat

Step-by-step instructions for safely removing the old thermostat from the wall.

Installing the Thermostat

Detailed procedures for mounting and wiring the new thermostat correctly.

Terminal Designator Explanations

Explanation of the function for each terminal on the thermostat's wiring base.

Important Safety Precautions

Critical safety warnings and handling instructions for the thermostat.

Thermostat Testing and Settings

Configuration Mode Settings

How to access and adjust advanced configuration settings for system compatibility.

Troubleshooting

Troubleshooting Common Issues

Guidance on diagnosing and resolving common problems with the thermostat.

Overview

The Amana 2246008 is a programmable electronic thermostat designed for efficient control of heating and cooling systems in residential and light commercial settings. This device supports 2-stage heat and 2-stage cool systems, including heat pumps, and is compatible with gas, oil, or electric heating. Its primary function is to maintain a desired indoor temperature according to user-defined schedules, offering flexibility and energy savings.

Function Description

The thermostat operates by sensing the ambient room temperature and comparing it to the user-set temperature (setpoint). When the room temperature deviates from the setpoint, the thermostat activates the appropriate heating or cooling stage to bring the temperature back to the desired level. It features auto changeover, allowing it to automatically switch between heating and cooling modes as needed, based on the setpoints for both. The device also includes an anti-short cycle delay to protect the compressor from rapid cycling, thus extending its lifespan.

The Amana 2246008 is highly configurable to match various HVAC system types. Users can select between Fahrenheit or Celsius temperature scales and adjust settings for different heat pump configurations (one or two compressors, with or without electric backup), as well as conventional heat/cool systems. The thermostat provides relay outputs for controlling the fan, first and second stages of heating, and first and second stages of cooling.

An optional indoor remote sensor can be connected to the thermostat to measure temperature in a different location, which is useful if the thermostat itself is not in an ideal spot for accurate temperature readings. The thermostat can also display the outdoor temperature if an optional outdoor sensor is installed.

Usage Features

The Amana 2246008 offers a user-friendly interface with a large display and backlight for easy readability, even in low light conditions. The display shows the current room temperature, setpoint, system mode (Heat, Cool, Auto, Off), fan mode (Auto, On), and various icons indicating active functions like lock mode, outdoor sensor activation, and temperature offset.

Programming and Scheduling:

The thermostat supports flexible programming options:

  • 7-Day Programming: Allows for a unique schedule for each day of the week.
  • 5-2-Day Programming: Provides one schedule for weekdays (Monday-Friday) and another for weekends (Saturday-Sunday).
  • 5-1-1-Day Programming: Offers one schedule for weekdays, and separate schedules for Saturday and Sunday.

Users can set up to four periods per day (Wake, Leave, Return, Sleep) with different temperature setpoints for each period, optimizing comfort and energy use throughout the day. The programming is intuitive, guided by on-screen prompts and button controls.

System Modes:

  • OFF Mode: Turns off all heating and cooling functions. The fan can still be operated manually.
  • HEAT Mode: Activates only the heating system. The thermostat will maintain the heat setpoint.
  • COOL Mode: Activates only the cooling system. The thermostat will maintain the cool setpoint.
  • AUTO Mode: Automatically switches between heating and cooling to maintain both heat and cool setpoints within a defined deadband. This mode is ideal for climates with fluctuating temperatures.

Fan Modes:

  • AUTO Fan: The fan runs only when the heating or cooling system is actively operating.
  • ON Fan: The fan runs continuously, regardless of whether the heating or cooling system is active.

Configuration Mode:

The configuration mode allows users to customize various operational parameters to suit their specific system and preferences. Key settings include:

  • Temperature Scale: Fahrenheit or Celsius.
  • Temperature Differential: Adjusts the temperature difference between the setpoint and when the system turns on (1st stage) and between the 1st and 2nd stages.
  • Staged Off Outputs: Determines if heating/cooling outputs turn off independently or simultaneously.
  • Minimum Deadband: Sets the minimum temperature separation between heat and cool setpoints in Auto mode.
  • System Type: Configures for heat pump (with O or B reversing valve, 1 or 2 compressors) or non-heat pump (gas/electric).
  • Auxiliary Delay ON: Sets a delay for auxiliary heat to engage after a call for 2nd stage heat, allowing the heat pump to try and satisfy the call first.
  • Lockout: Allows for keypad lockout to prevent unauthorized changes to settings, with options to limit setpoint adjustment or lock out during NITE periods.
  • Maximum Heat Setpoint/Minimum Cool Setpoint: Defines the allowable range for temperature setpoints.
  • Room Temperature Offset: Calibrates the displayed room temperature to match the actual room temperature.
  • Maximum Cycles Allowed Per Hour: Limits the number of times the system can cycle on/off within an hour to protect equipment.
  • Temperature Sensor: Selects whether to use the on-board sensor, remote sensor, an average of both, or switch between them during NITE periods.
  • Cooling Fan Delay Off Time: Sets a fan purge time after the cooling cycle ends.

Maintenance Features

The Amana 2246008 is designed for minimal maintenance. Regular cleaning of the thermostat cover is recommended to ensure proper sensor operation. The device includes a reset switch that can be used to restore factory default settings if needed, which can be helpful for troubleshooting or reconfiguring the thermostat.

The thermostat is designed for easy installation, with clear wiring diagrams provided for various system configurations. The terminal designators are clearly labeled, simplifying the connection process. For optimal performance, it is important to follow the installation guidelines, such as mounting the thermostat in an appropriate location away from direct sunlight, drafts, or heat sources.

In case of operational issues, the manual provides a troubleshooting guide that lists common problems and their corresponding remedies, such as checking power, wiring connections, and configuration settings. The device's robust design and configurable features contribute to its long-term reliability and ease of use.

Amana 2246008 Specifications

General IconGeneral
Stages1 Heat/1 Cool
DisplayDigital
ProgrammabilityNon-Programmable
Power SourceBattery
Voltage24 VAC
ProgrammableNo

Related product manuals