EasyManuals Logo

Amana AVPEC Series User Manual

Amana AVPEC Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23
TROUBLESHOOTING
b4 E_b4
BLower Motor Trip
or Lost Rotor
(MOTOR TRIPS)
Blower Motor -
Current Trip (or) Lost Rotor
• Fan/motor obstruction or abnormal motor loading
Power interruption (low voltage)
High loading conditions, blocked filters
• Blockage in the airflow (ductwork) or ductwork undersized
b6 E_b6
Voltage or Temperature Trip
(MOTOR VOLTS)
• Blower motor stops for over/under
voltage
• Bower motor stops due to PCB
over heating
High AC line voltage to ID blower
Low AC line voltage to ID blower
High ambient temperatures
Incorrect wiring
• Fan/motor obstruction or blockage in the airflow
b7 E_b7
Incomplete Parameters
Sent to Motor
(MOTOR PARAMS)
ID blower motor does not have
required parameters to function.
• Wrong / no shared data on the network
Locked motor rotor condition
b9 E_b9 No Display
Low Indoor Airflow
(without Electric Heat mode)
Fan/motor obstruction or blocked filters
Restrictive ductwork or ductwork undersized
W iring disconnected
Wrong outdoor/indoor combination
• ID motor failure
9b E_9b LOW ID AIR EH MODE
Low Indoor Airflow
(with Electric Heat mode)
Fan/motor obstruction or blocked filters
Restrictive ductwork or ductwork undersized
• ID motor failure
W iring disconnected
70 E_70 EEV OPEN CKT EEV disconnection detected
• Indoor EEV coil not connected
Incorrect wiring to EEV
73 E_73 LIQ TEMP FLT Liquid side thermistor abnormality
• Open (or) short circuit of the liquid thermistor (X5A)
• Liquid thermistor reading incorrect or values outside the normal range
74 E_74 GAS TEMP FLT Gas side thermistor abnormality
• Open (or) short circuit of the gas thermistor (X5A)
• Gas thermistor reading incorrect or values outside the normal range
75 E_75 PRESSURE FLT Pressure sensor abnormality
• Open (or) short circuit of the Pressure sensor (X15A)
• Pressure sensor reading incorrect or values outside the normal range
77 E_77 TSTAT ID NO COM
Indoor Unit - Thermostat
communication error
(start-up & during operation)
• Incorrect wiring between ID unit and thermostat.
The system may have the communication error without error code 77
on the indoor PCB. Follow section 16.6 SYSTEM TROUBLESHOOTING
Thermostat failure
Power interruption (low voltage)
Error
Code
De sc ri pti on Possi bl e Ca use sClimateTalk MessagePCB LED Display
• Check for obstruction on the fan/motor/ductwork
• Verify the input voltage at the motor
• Check filters, grills, duct system, coil air inlet/outlet for blockages.
• Replace motor
• Verify line voltage to blower is within the range specified on the ID blower rating plate
• See "Installation Instructions" for installation requirements
• Check power to air handler blower
• Check for obstruction on the fan/motor/ductwork
Check wiring
Replace motor
• Check for locked rotor condition (see above error code for details)
Replace circuit board or motor
• Check for obstruction on the fan/motor
• Check ductwork/filter for blockage, clean filters
Remove obstruction. Verify all registers are fully open
• Check the connections and the rotation of the motor
• Verify the input voltage at the motor
• Verify ductwork is appropriately sized for system. Resize/replace ductwork if needed
Replace motor
• Check for obstruction on the fan/motor
• Check ductwork/filter for blockage, clean filters
Remove obstruction. Verify all registers are fully open
• Check the connections and the rotation of the motor
• Verify the input voltage at the motor
• Verify ductwork is appropriately sized for system. Resize/replace ductwork if needed
Replace motor
• Check Indoor EEV coil connection (PCB and junction connector)
Replace EEV coil
• Check the resistance value of EEV coil (refer service manual)
Replace the control board
• Check the connection to liquid thermistor (PCB and junction connector)
• Check the resistance value of the thermistor (refer service manual)
Replace thermistor
Replace the control board
• Check the connection to gas thermistor (PCB and junction connector)
• Check the resistance value of the thermistor (refer service manual)
Replace thermistor
Replace the control board
• Check the connection to pressure sensor (PCB and junction connector)
• Check the output voltage of the pressure sensor (refer service manual)
Replace pressure sensor
Replace the control board
• Check for thermostat and indoor unit wiring
• Verify the input voltage at the ID unit and thermostat
After recovering the system with power supply, TSTAT ID NO COM will continue to be
displayed on the thermostat within 2 minutes. The error code will be cleared automatically.
• Replace control board or thermostat
• Press "LEARN" button on PCB for more than 5 seconds to reestablish network
Corre ctive Actions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Amana AVPEC Series and is the answer not in the manual?

Amana AVPEC Series Specifications

General IconGeneral
BrandAmana
ModelAVPEC Series
CategoryAir Handlers
LanguageEnglish

Related product manuals