SERVICING
SET THERMOSTAT TO PUMP DOWN
PUMP DOWN operation is designed for line set less
than 80 feet in length. Do not start
operation if line set length is 80 feet or more.
Piping may burst as a result.
PUMP DOWN
Please follow the following sequence to enter PUMP DOWN to
accumulate the refrigerant to outdoor unit.
Do not operate COOL ON or HEAT ON mode to enter PUMP DOWN.
Before starting the PUMP DOWN operation, change indoor fan
trim, delay and profile back to default and stop electric heater .
Remove if no trim feature. In this operation, the gas valve and
liquid service valve should be opened.
NOTE: Manufacturer recommends to set PUMP DOWN using 7-
segment display. For more information, see section Set 7-segment
mode display to PUMP DOWN. If difficulty is encountered using
7-segment display, use the thermostat as an alternative method.
See section "SET 7-SEGMENT MODE DISPLAY TO PUMP DOWN".
1. On the HOME screen, select MENU.
2. From the MENU screen, select COMFORTNET USER MENU.
3. Enter installer password. (The password is the Date Code
located on the thermostat and is available by entering the
EQUIPMENT STATUS menu and scrolling to the bottom.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Amana AVZC180241 Series and is the answer not in the manual?

Amana AVZC180241 Series Specifications

General IconGeneral
BrandAmana
ModelAVZC180241 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals