EasyManuals Logo

Ametek Powervar Security Plus II User Manual

Ametek Powervar Security Plus II
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
A01-00150 Rev B
11
1 - 3 are Static Switch Output (SSO) Tap selections (must match
mains inv voltage selection)
- Terminal block Position 3 is called SSO or 0
4; 5; 6; 7 Next four are outputs as listed 120; 88; 0; 120
8; 9; 10 Last three are mains power input L1; L2; earth
CAUTION
For field wired units, refer to the tables below for the proper conductor
size and torque requirements. Only copper conductors are to be used for
field wiring connections. The conductors should be rated at least 75°C
or greater. The conductor recommendations listed in the chart below are
intended for installations in North America. For international installations,
please refer to the local and national electrical codes and standards.
INPUT
CONDUCTOR
(AWG)
OUTPUT
CONDUCTOR
(AWG)
GROUND
(AWG)
RATING MIN MAX
TORQUE
(in-lbs)
MIN MAX
TORQUE
(in-lbs)
MIN MAX
TORQUE
(in-lbs)
2.0kVA
12
6
20
12
6
20
12
6
20
3.0kVA
12
6
20 12
6
20 12
6
20
4.0kVA
10
6
20 10
6
20
8
6
20
5.2kVA
8
6
20
8
6
20
8
6
20
6.0kVA
8
6
20
8
6
20
6
6
20
8.0kVA
4
1
60
4
1
60
6
4
60
10.0kVA
4
1
60
4
1
60
6
4
60
TABLE 2-4A HIGH VOLTAGE CONDUCTOR SIZE AND TORQUE SPECIFICATIONS
INPUT
CONDUCTOR
(AWG)
OUTPUT
CONDUCTOR
(AWG)
GROUND
(AWG)
RATING MIN MAX
TORQUE
(in-lbs)
MIN MAX
TORQUE
(in-lbs)
MIN MAX
TORQUE
(in-lbs)
2.0kVA
10
6
20 10
6
20
8
6
20
3.0kVA
8
6
20
8
6
20
6
4
20
TABLE 2-4B LOW VOLTAGE CONDUCTOR SIZE AND TORQUE SPECIFICATIONS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ametek Powervar Security Plus II and is the answer not in the manual?

Ametek Powervar Security Plus II Specifications

General IconGeneral
BrandAmetek
ModelPowervar Security Plus II
CategoryUPS
LanguageEnglish

Related product manuals