EasyManua.ls Logo

Ametek XPD 7.5-67 - Page 49

Ametek XPD 7.5-67
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 3. Local Operation
User Diagnostics
47
Output voltage
fluctuating or
regulation poor.
Is unit at current limit? Increase current limit setting or
reduce load. See
“Standard
Operation” on page 35
.
Is input voltage within
specified range?
Connect to appropriate AC voltage
source. See
“AC Input Power
Connection” on page 28
.
Are sense lines
connected?
See
“Load Connection” on page
30
, and “Remote Sensing” on
page 33
.
is unit under remote
analog control?
Ensure that program source is
stable.
Internal circuit. See your service technician.
Output oscillating. Internal circuit. See your service technician.
Symptom Check Further Checks and Corrections

Table of Contents

Related product manuals