DEHUMIDIFER CONTROL
ON/OFF BUTTON
USED TO TURN
DEHUMIDIFIER ON
AND OFF
UP/DOWN
BUTTONS USED TO
CHANGE HUMIDITY
SETTING
MODE BUTTON
USED FOR
OPTIONAL FEATURES
INLET
FILTER
OUTLET
SAFETY INSTRUCTIONS
WARNING
1. High voltage may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power
disconnected until installation/service is completed.
2. Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling duct work.
3. Dropping may cause personal injury or equipment damage. Handle with care and follow installation instructions.
CAUTION
1. Read all instructions before beginning installation.
2. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible
for their safety. Children should be supervised to ensure that they do not play with the appliance.
3. Do not use in pool applications. Pool chemicals can damage the dehumidifier.
4. Do not use solvents or cleaners on or near the circuit board. Chemicals can damage circuit board components.
5. Wait 24 hours before running the unit if it was not shipped or stored in the upright position
6. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
READ AND SAVE THESE INSTRUCTIONS
Model A320V1 and A320V3 Dehumidifier
Installation and Operating Instructions
90-2432
10013678 B2208381E 10.21
English 1

Other manuals for Anden A320V1

Questions and Answers

  • H
    Heather ZimmermanAug 17, 2025
    Why is my Anden A320V1 Dehumidifier producing hot air?
    • G
      gwilsonAug 18, 2025
      It's normal for the Anden Dehumidifier to produce hot air. The air is reheated as it passes across the condenser coil, which causes the temperature to rise between the inlet and outlet.
  • C
    cervanteswandaAug 20, 2025
    How to fix Anden A320V1 Dehumidifier blower running but with little or no airflow?
    • R
      Ryan Flores DDSAug 20, 2025
      If your Anden Dehumidifier blower is running with little to no airflow, you should: * Check the dehumidifier's air filter and replace it if needed. * Inspect the ductwork for any blockages and clear them. * Make sure that the outlet collar with backflow damper is installed on the outlet side of the dehumidifier. * Check the backflow damper for any obstructions or if it's stuck, and remove any blockage.
  • B
    bjohnsonAug 22, 2025
    What to do if my Anden A320V1 does not turn on?
    • L
      Lauren SanchezAug 22, 2025
      If your Anden Dehumidifier is not turning on, make sure that: * The dehumidifier is properly plugged in. * The power switch is in the ON position. * The control is turned ON. * The circuit breaker hasn't tripped.
  • J
    jenniferdoyleAug 25, 2025
    Why is my Anden A320V1 Dehumidifier not draining properly?
    • L
      Laura BlackAug 26, 2025
      If your Anden Dehumidifier is not draining properly, first ensure that the unit is level. Then, check the drain line for any blockages and make sure it has a continuous downward slope.
  • A
    Amanda SmithAug 27, 2025
    How to stop coil frosting in my Anden A320V1 Dehumidifier?
    • W
      williamsangelaAug 27, 2025
      If your Anden Dehumidifier's coil is frosting, it may be due to: * Lack of or reduced airflow: Check the air filter and wash or replace it. * Blocked ductwork: Inspect the ductwork for blockages. * Inlet air conditions below 60°F: Increase the humidity setting.
  • B
    Brian HerreraAug 30, 2025
    What causes the Anden A320V1 blower to run but the compressor not?
    • J
      Jennifer RichardsonAug 30, 2025
      If the Anden Dehumidifier blower is running, but the compressor isn't, check the connections at the control board and empty the condensate pan if a float switch is installed. If there is no float switch installed, ensure the jumper is installed at the float switch terminals on the control board.
  • J
    James OwensSep 1, 2025
    What does error E7 mean on my Anden Dehumidifier and how do I fix it?
    • C
      Cynthia CostaSep 2, 2025
      If the Anden Dehumidifier displays error code E7, you should empty the condensate pan and check the float switch connection at the control board. If you are not using a float switch, verify that the jumper is between the float switch terminals on the dehumidifier control board. If the problem continues, consider replacing the float switch.
  • T
    Tricia RamirezSep 4, 2025
    How to troubleshoot error code E4 on Anden Dehumidifier?
    • D
      David DavidsonSep 4, 2025
      If the Anden Dehumidifier displays error code E4, check the frost sensor connection at the power board and ensure the terminal is fully seated. Remove the side access panel and verify that the sensor is secured to the suction line. Reset the fault by cycling power to the dehumidifier. Turn the humidity setting down (below room/home humidity level) to make a dehumidification call. Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic test mode. Record values and call Technical Support.
  • A
    Andrea DavisSep 6, 2025
    What does error code E5 mean on my Anden Dehumidifier?
    • R
      rflynnSep 6, 2025
      If the Anden Dehumidifier displays error code E5, check the high temperature sensor connection at the power board, ensuring the terminal is fully seated. Remove the side access panel and verify the sensor is not damaged and is connected to the refrigeration line coming from the compressor. It may need to be replaced with Part No. 5456 – contact Technical Support to confirm.
  • A
    Arthur TurnerSep 9, 2025
    How do I fix error code E6 on my Anden Dehumidifier?
    • J
      juliahenrySep 9, 2025
      If the Anden Dehumidifier displays error code E6, check the low temperature sensor connection at the power board. Remove the side access panel and verify the sensor is not damaged and connected to the suction line. It may need to be replaced with Part No. 5455 – contact Technical Support to confirm.

Summary

Safety Instructions

Specifications

Suspending the Dehumidifier

Drain Installation

Condensate Pan, Condensate Pump and Float Switch

Hard Wiring - Line Voltage

Start Up and Sequence of Operation

Using the Dehumidifier Control

Steps and logic for operating the dehumidifier using its on-board control interface.

Using the Model A77 Control

Instructions for operating the dehumidifier when controlled by the Model A77 external unit.

System Set-Up & Checkout

Wiring and Set-up

Alternative External Control

Daisy Chain Wiring

Alternate External Dry Contact Control as Driving Control

Codes

Troubleshooting

Diagnostic Codes

Lists and explains error codes displayed by the dehumidifier for fault identification.