EasyManua.ls Logo

Andover Controls SCX 920 - Page 16

Default Icon
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Installation
8 SCX 920 Installation Guide
Table 1 shows the maximum runs for wires of various gauges to keep
errors within .5°F, .25°F, and .10°F when sensing temperatures up to
70°F.
Table 2 shows the maximum runs for wires of various gauges to keep
errors minimal when sensing temperatures up to 100°F.
Table 1. Wire Gauges and Corresponding Maximum Runs
for Sensing Temperatures Up to 70
°
F
Gauge
1
/
2
°
F Error
1
/
4
°
F Error
1
/
10
°
F Error
#14 26,700 ft 13,300 ft 5300 ft
#16 16,800 ft 8400 ft 3300 ft
#18 10,500 ft 5200 ft 2100 ft
#20 6600 ft 3300 ft 1300 ft
#22 4100 ft 2000 ft 800 ft
Table 2. Wire Gauges and Corresponding Maximum Runs
for Sensing Temperatures Up to 100
°
F
Gauge
1
/
2
°
F Error
1
/
4
°
F Error
1
/
10
°
F Error
#14 12,700 ft 6300 ft 2500 ft
#16 7900 ft 3900 ft 1500 ft
#18 5000 ft 2500 ft 1000 ft
#20 3100 ft 1500 ft 600 ft
#22 1900 ft 900 ft 300 ft