Hardware Installation
18 SCX 920 Installation Guide
2. Disconnect the jumper end from E7 and move it to E5 so it jumpers
E2 to E5.
3. Leave the other jumper as it is.
To change the voltage from 115 V to 230 V, proceed as follows:
1. Disconnect the jumper from E1 to E4 and remove it.
2. Disconnect the jumper from E6 and connect it to E4, so it jumpers
TP10 to E4.
3. Leave the other jumper as it is.
Wiring the Infinet to the SCX 920
Note
You must use shielded cables for Infinet to ensure compliance with the
Class A FCC limits and to ensure reliable communications.
Figure 5 illustrates how to wire the Infinet cable to the removable block
terminal connector in the lower left corner of the SCX 920.
Figure 5. Infinet Cable Wiring
1. Trim back the shield over the wires.
2. Take the first wire for the incoming Infinet and the first wire for the
outgoing Infinet and slip both in the hole beneath the screw labeled
with a plus sign (top).
+
–
SHLD
Infinet Connection
WHITE
WHITE
BLACK
BLACK