Hardware Installation
SCX 920 Installation Guide 17
Figure 4. Metal Plate and Screw for Power Supply Wire
3. Place the white wire under the metal plate behind the middle screw,
labeled NEU.
4. Tighten the screw with a flathead screw driver.
5. Place the black wire under the metal plate behind the bottom screw,
labeled HOT.
6. Tighten the screw with a flathead screw driver.
Selecting the AC Input Voltage
The voltage is set to 115 V when shipped. To change the voltage, you
must reset the jumpers to the right of the AC power cord connection.
Table 4 shows jumper settings for the three voltages.
To change the voltage from 115 V to 24 V, proceed as follows:
1. Disconnect the jumper end from E4 and move it to E3 so it jumpers
E1 to E3.
Table 4. Connecting Jumpers for AC Input Voltages
24V Jumpers 115V Jumpers 230V Jumpers
From To From To From To
E1 E3 E1 E4 — —
E2 E5 E2 E7 E2 E7
TP 10 E6 TP 10 E6 TP 10 E4
Insert Wire Here
Metal Plate
Technical Manuals Online! - http://www.tech-man.com