Hardware Installation
SCX 920 Installation Guide 9
Table 3 shows the maximum runs for wires of various gauges to keep
errors minimal when sensing temperatures up to 150°F.
Laying Out the Site Setup
You may want to draw a map of where you plan to put each controller
and store it in a notebook.
Find the tag attached to each controller that gives the number of the con-
troller. Before you remove any tags, be sure the tag has all of the
following information on it:
Location of the controller.
Serial number.
Model name and number.
Communications port the Infinet connects to on Infinity CX 9000.
Then collect the tags. You will need to know where your controllers are
located when you later assign a name to each controller and each input
and output.
Table 3. Wire Gauges and Corresponding Maximum Runs
for Sensing Temperatures Up to 150
°
F
Gauge
1
/
2
°
F Error
1
/
4
°
F Error
1
/
10
°
F Error
#14 4100 ft 2000 ft 800 ft
#16 2600 ft 1300 ft 500 ft
#18 1600 ft 800 ft 300 ft
#20 1000 ft 500 ft 200 ft
#22 650 ft 300 ft 130 ft