Hardware Installation
20 SCX 920 Installation Guide
Caution
Although inputs usually function properly with unshielded sensor wire,
you may need shielded wire if you run the wire as follows:
In the same conduit with other noise-generating conductors such as
60 Hz AC power.
In long runs close to large power-consuming or power-generating
equipment that can produce 60 Hz noise.
We recommend you run input wiring in a conduit separate from AC
power or output wiring and avoid long wiring runs.
Caution
Follow the rules below when wiring inputs and outputs:
Never lay wires across the surface of the printed circuit board. You
should bring input wires in from the left and output wires in from the
right.
Bundle excess wires toward the back of the cabinet to avoid any
contact with circuit boards.
Wires should never be within 1 in. of any component on the printed
circuit board.
Keep cabinet free of foreign materials (extra power supplies, relays,
and so on).
Be careful when stripping wire not to drop small pieces of wire
inside the cabinet.
If you violate any of these rules, the controller could malfunction.
Caution
Never apply a voltage to a thermistor. Doing so alters the thermistor’s
accuracy and reliability. You should replace a thermistor that has had
voltage applied to it. Never bring a soldering iron to within 3 inches of
the thermistor’s sensing tip.