20
5.5.2 Option Switch 2
Option Switch 2 functions differently for different versions of the UPS.
100 Vac version
No function; not used.
120 Vac version
The UPS’s factory-set input voltage limits for on-line and SmartBoost
operation are centered on the nominal input voltage of 120 Vac (see also
Sec. 9.1). When Option Switch 2 is set to the on ( I ) position, the upper and
lower transfer voltages are lowered by 4% and centered on a nominal input
of 115 Vac. This is useful where nominal input voltage is 110 to 115 Vac.
220/230/240 Vac version
The UPS’s factory-set on-battery output voltage and input voltage limits for
on-line and SmartBoost operation are designed for use in regions where the
nominal line voltage is 220 to 230 Vac. When Option Switch 2 is set to the
on ( I ) position, the upper and lower transfer voltages are raised by 4% and
centered on a nominal input of 240 Vac. In addition, the on-battery output
voltage is increased to 240 Vac.
5.5.3 Option Switch 3
When Option Switch 3 is set to the on ( I ) position, the UPS’s audible alarm
is disabled for the first 30 seconds of on-battery operation. This function is
useful where brief power interruptions are frequent and cause the alarm to
become annoying.
5.5.4 Option Switch 4
When Option Switch 4 is set to the on ( I ) position, the UPS’s low-battery
alarm interval is extended from 2 minutes (factory setting) to 5 minutes.
This function is useful if the UPS is protecting a computer system that
requires more than 2 minutes warning to perform a graceful shutdown.
5.0 Operation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC 600 and is the answer not in the manual?

APC 600 Specifications

General IconGeneral
Nominal Output Voltage230V
Nominal Input Voltage230V
Output Power Capacity360 Watts / 600 VA
Frequency50/60 Hz
Input ConnectionsIEC 320 C14
Typical Recharge Time6 hours
Battery TypeMaintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof