CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
APC Symmetra LX
GUIDE SPECIFICATIONS FOR
4kVA-16kVA
Uninterruptible Power System
PART 1 - GENERAL
1.1 SUMMARY
A. This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS.
B. The UPS shall utilize modular power protection technology designed to allow internal
redundancy, scalability of power and runtime, and fast mean time to repair (MTTR).
The UPS should be configured from five basic components- UPS frames, extended run
battery frames (XR frames), power modules, battery modules, and intelligence modules.
UPS and XR frames should be capable of shipping with modules installed. XR frames
should be capable of communicating battery and runtime status to intelligence modules.
Power, battery, and intelligence modules should be hot-swappable and user-replaceable
for fast MTTR.
C. Configuration Specifics:
1. The UPS frame(s) should be capable of the following configurations:
____4-8kVA N+1 Redundant Tower
____4-16kVA N+1 Redundant Tower
____4-16kVA N+1 Redundant Tower with nine (9) extra Battery Module slots
____4-8kVA N+1 Redundant 13U Rack-mount
____4-16kVA N+1 Redundant 19U Rack-mount
2. The system power train shall be comprised of hot-swappable, user-replaceable
3.2kW/4kVA and 10% Battery charger circuit power modules, which shall
operate in parallel, and be configurable for N+1 redundant operation at rated
load.
3. The system shall also include a field-replaceable internal automatic and manual
bypass system module, field-replaceable output power distribution panels,
removable input/output wiring tray, standard redundant intelligent modules,
battery disconnects, an LCD interface display, EPO, and an integrated UPS
network management card with temperature monitoring.
D. In addition, this specification describes the performance, functionality, and design of
the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery
Systems, and connectivity solutions.
Question and Answer IconNeed help?

Do you have a question about the APC LX and is the answer not in the manual?

APC LX Specifications

General IconGeneral
BrandAPC
ModelLX
CategoryPower Supply
LanguageEnglish

Summary

PART 1 - GENERAL

1.1 SUMMARY

This specification describes the operation and functionality of a continuous duty, single-phase, static Uninterruptible Power System (UPS).

1.2 STANDARDS

Lists compliance with UL 1778, CSA, FCC Class A, ISO 9001, and ISO 14001 standards.

1.3 MODES OF OPERATION

Details Normal, Battery, Recharge, Automatic Bypass, and Manual Bypass modes of operation.

1.4 SUBMITTALS

Outlines requirements for Proposal Submittals (bill of materials, catalog sheets, etc.) and Delivery Submittals (installation, user manuals).

PART 2 - PRODUCT

2.1 DESIGN REQUIREMENTS

Specifies initial and final capacity, and battery sizing requirements for the UPS.

2.2 SYSTEM CHARACTERISTICS

Details system capacity, input/output voltage, frequency, power factor, distortion, overload, and efficiency.

2.3 ENVIRONMENTAL

Defines storage and operating temperature ranges, humidity, and altitude limits for the UPS.

2.4 INPUT POWER CONVERTER

Describes the function, THD, current limit, redundancy, and charging of input converters.

2.6 OUTPUT INVERTER

Covers inverter waveform creation, overload capability, output contactor, battery protection, and redundancy.

2.7 AUTOMATIC BYPASS

Describes the system automatic bypass switch, its transfer capability, and monitoring functions.

2.8 DISPLAY AND CONTROLS

Details control logic, display unit features, metered data, event logs, and alarm conditions.

2.9 BATTERY

Details modular battery construction, VRLA type, management system, and hot-swappable modules.

PART 3 - ACCESSORIES

3.1 SERVICE BYPASS PANEL (SBP)

Provides power to the critical load bus from the bypass source during maintenance or service of the UPS frame.

3.2 REMOVABLE INPUT;OUPUT ELECTRICAL TERMINAL

The input and output terminal connections are designed to be a removable tray for easy electrical connection.

3.4 SOFTWARE AND CONNECTIVITY

Covers Network Adaptor for monitoring/management and Unattended Shutdown capabilities.

PART 4 - EXECUTION

4.1 FACTORY ASSISTED START-UP

Details inspections, test procedures, and on-site training performed by factory trained personnel.

4.2 MANUFACTURER FIELD SERVICE

Outlines worldwide service availability, including start-up, maintenance, and replacement parts.

4.3 MAINTENANCE CONTRACTS

Describes offerings for preventative and full service maintenance contracts for the UPS and battery systems.

4.4 TRAINING

Details the UPS service training workshop, including lectures, practical instruction, and laboratory sessions.