The following symbols appear in this User's Manual:
CAUTION/DANGER - Caution indicates risk of
bodily harm. Danger indicates that a risk of elec-
trical shock is present and the associated proce-
dures should be followed carefully.
STAND BY MODE - The system enable switch,
and the input circuit breaker use the stand by
mode. When either of these are switched to stand
by, the Power Array is disconnected from mains
(utility) input voltage. In this mode, the system
appears to be off, although the mains (utility)
power is still connected to the system. For this
reason, the standby mode is unsafe for servicing
the system. Always follow the five step Total Power
Off procedure before servicing the Power Array.
(See procedure at right.)
OFF POSITION - The maintenance bypass
switch is the only switch that can be placed in the
off position. When switched to the off posi-
tion, the Power Array functions normally, receiv-
ing mains (utility) power, and delivering condi-
tioned power to the load equipment.
ON POSITION - All three switches (The sys-
tem enable switch, the maintenance bypass switch
and the input circuit breaker) can be placed in the
on position. See the description for each of these
switches in Chapter 1.
SAFETY EARTH GROUND - Indicates the pri-
mary safety ground.
Safety
Safety-1
IMPORIMPOR
IMPORIMPOR
IMPOR
TT
TT
T
ANT SAFETY INSTRUCTIONSANT SAFETY INSTRUCTIONS
ANT SAFETY INSTRUCTIONSANT SAFETY INSTRUCTIONS
ANT SAFETY INSTRUCTIONS
n SAVE THIS USER MANUAL - This manual contains im-
portant instructions that should be followed during in-
stallation and maintenance of the Power Array, and for
installation or replacement of the battery and power mod-
ules.
CONSERVER CES INSTRUCTIONS. CETTE NOTICE
CONTIENT DES INSTUCTIONS IMPORTANTES
CONCERNANT LA SÉCURITÉ.
n Connection to the branch circuit (mains utility power
source) must be performed by a licensed electician.
n Installation of the power and battery modules can be per-
formed by any individual with no previous technical ex-
perience.
n Operation of the Symmetra
TM
can be performed by any
individual with no previous technical experience.
n The protective earth conductor for the Symmetra
TM
car-
ries the leakage current from the load devices (computer
equipment). Therefore, the size of the conductor must be
at least as large as the wire required by IEC 950. IEC 950
states the following nominal cross-sectional areas:
- 2.5 mm
2
for rated current between 17 & 25 A
- 6 mm
2
for rated current between 33 & 40 A
- 10 mm
2
for rated current between 41 & 63 A
- 16 mm
2
for rated current between 64 & 80 A
n FIVE STEP TOTAL POWER OFF PROCEDURE
To remove all power from the Power Array (Total Power
Off), the following events must occur in the order listed:
1. Set system enable switch to the stand by position.
2. Set input circuit breaker to the stand by position.
3. Remove all battery modules from the Power Array.
4. Disconnect XR external battery cabinet (if present).
5. Disconnect the mains/branch circuit breaker.