Rear VRear V
Rear VRear V
Rear V
iew of a Power Ariew of a Power Ar
iew of a Power Ariew of a Power Ar
iew of a Power Ar
rayray
rayray
ray
The rear of a MiniFrame Power Array system is shown be-
low. (The rear of a MasterFrame is identical.) Each of the
components is described in a section that follows:
System Enable Switch
The system enable switch regulates power to the intelligence
modules. It does not power the load. When switched to the
on position, the Power Array enters the load-disconnect
operating mode. When switched to stand by, the intelli-
gence modules are disconnected from the mains voltage, and
the system shuts down.
Note: The load is not powered until the power the load com-
mand is entered into the PowerView user interface.
Communication Interface Ports
There are three interface ports: A Remote PowerView port
for the 6.1 m (20') RJ45 PowerView cable, a 9-pin computer
interface port for APC PowerChute Plus software, and a bat-
tery communication port for an XR Extended Run Frame.
Smart Slots
TM
Accessory Ports
APC manufactures a set of auxiliary user interface accesso-
ries, called SmartSlot
TM
devices. Four SmartSlot
TM
installa-
tion ports are provided. SmartSlot
TM
interface options include
the following:
n Protection and safe shutdown of multiple servers
n SNMP adaptor for accessing data via a network
n CallUPS
TM
- telephone notification of power event
n MeasureUPS
TM
- monitor environmental conditions
n Control and monitor Power Array via modem
Note: Use only SmartSlot
TM
devices labeled Symmetra
TM
Compatible.
REPO/Input/Output Wiring Access Panels
Wiring terminal blocks for input and output wiring and for
remote emergency power off (REPO) switch installations are
accessed through these panels.
Note: Wiring is to be installed by a qualified electrician only.
Convenience Power Panel
Eight IEC 320 C13 type power outlets are provided. The out-
lets are arranged in two sets of four. Each set is equipped with
a circuit breaker.
Extended Run Battery Frame Connector
An optional XR Extended Run Battery Frame can be connected
to the Power Array via this connector. See the Users Manual
included with the XR Extended Run Battery Frame.
Fig 1-10 Rear View of a Mini Frame Symmetra
TM
Power Array System
SmartSlot
TM
Accessory
Ports
MiniFrame
Input
Wiring
Access
Panels
Communication
Interface
Ports
Output
Wiring
Access
Panels
XR Extended Run
Battery Frame
Connector
System
Enable
Switch
1-4
Chapter 1 - Physical Representation
REPO Wiring
Access Panels
Convenience Power
Panel