The Power Array frame is 61cm (24") wide and 68.6cm (27")
deep. Refer to table 4-1 for the height and weight of fully
loaded systems.
eziSemarFeziSemarF
eziSemarF
eziSemarFeziSemarF thgieHthgieH
thgieH
thgieHthgieH
thgieWthgieW
thgieW
thgieWthgieW
dedaoLylluFdedaoLylluF
dedaoLylluF
dedaoLylluFdedaoLylluF
emarFiniM
mc7.87
"13
gk832
bl525
emarFretsaM
mc1.231
"25
gk914
bl529
Table 2-1 Height & Weight (Loaded w/ Modules)
Make sure there is adequate space and structural integrity to
support the fully loaded frame. Refer to figure 2-1. The weight
of the Power Array rests on four 3.8cm (1.5") diameter leveling
feet. Positions of the leveling feet are shown. When installing
the frame, allow 30.5cm (12") of clearance behind the frame
for adequate airflow. (Air flows in through the front of the
frame and out the back.) Allow 122cm (48") of clearance in
the front of the Symmetra
TM
to access the PowerView and to
install modules.
Fig 2-1 System Footprint and Required Clearance
Transporting Power Array to Installation Site
When it is shipped, the Power Array frame is bolted to a cus-
tom-designed pallet. The modules are stacked on either one
or two additional pallets. It is recommended that these pallets
be moved from the receiving dock to the installation area with
a pallet jack. Make sure there is enough space and structural
integrity to move these pallets.
Operating Conditions
The Power Array is intended for installation in a temperature
controlled indoor area that is free of conductive contaminants.
The operating evironment must be clean, dry, and protected.
The atmosphere must be free of dust and corrosive fumes.
Adequate airflow must be provided for the operation of the
system. Make sure environmental conditions are within the
following parameters:
n Relative Humidity: 0 to 95%, non-condensing.
n Temperature: 0°C to 40°C (32°F to 104°F).
n Elevation: 0m to 3,048m (0ft to 10,000ft).
n Electro-Static Discharge (ESD) Susceptibility: The Power
Array and all modules are capable of withstanding
through air electro-static discharges up to an ampli-
tude of +/-15kV and direct discharge electro-static dis-
charges up to an amplitude of +/-8kV without failure,
abnormal operation, or degradation in performance. ESD
test methods conform to IEC 801-2.
BTU Output
Refer to table 2-2 for BTU output of a fully loaded Power
Array system. The BTU output is significantly higher while
the batteries are charging. Under normal operating condi-
tions, battery recharge periods are relatively infrequent.
emarFemarF
emarF
emarFemarF
eziSeziS
eziS
eziSeziS
rH/UTBrH/UTB
rH/UTB
rH/UTBrH/UTB
((
(
((
seirettabseirettab
seirettab
seirettabseirettab
yllufylluf
ylluf
yllufylluf
)degrahc)degrahc
)degrahc
)degrahc)degrahc
rH/UTBrH/UTB
rH/UTB
rH/UTBrH/UTB
((
(
((
,gnigrahcseirettab,gnigrahcseirettab
,gnigrahcseirettab
,gnigrahcseirettab,gnigrahcseirettab
yticapacemarfllufyticapacemarflluf
yticapacemarflluf
yticapacemarfllufyticapacemarflluf
eludom1+Nhtiweludom1+Nhtiw
eludom1+Nhtiw
eludom1+Nhtiweludom1+Nhtiw
)noitarugifnoc)noitarugifnoc
)noitarugifnoc
)noitarugifnoc)noitarugifnoc
emarFiniM314,3076,8
emarFretsaM628,6046,51
Table 2-2 BTU Output
Temporary Storage of Modules
The battery and power modules must be temporarily stored
until the frame is permanently installed. To preserve battery
life, always store batteries in a cool, dry place.