screen has been reviewed, press the Enter key. The percent
load with redundancy status screen appears.
% Load With Redundancy Status Screen
Fig 7-7 Percent Load With Redundancy Status Screen
% Load Allowing For Redundancy - displays the percent of
the non-redundant Power Array capacity that is required by
the load. The non-redundant Power Array capacity is de-
fined by the number of user defined non-redundant power
modules installed multiplied by 4kVA, and it is limited by
the kVA rating of the frame. See table 7-1. After the load
with redundancy status screen has been reviewed, press the
Enter key. The frequency status screen appears.
Note: The redundancy level for this measurement is user de-
fined and will be assigned in step 6 of this procedure. Either
zero, one, or two of the power modules will be designated as
redundant. The remaining power modules are then defined
as non-redundant.
Table 7-1 Non-Redundant Power Array Capacities
Frequency Status Screen
Fig 7-8 Frequency Status Screen
Frequencies - displays the input frequency that is being re-
ceived from the utility power source and the output frequency
being delivered to the load equipment. After the frequency
status screen has been reviewed, press the Enter key. The bat-
tery status screen appears.
Battery Status Screen
Fig 7-9 Battery Status Screen
Battery Status Screen - displays battery voltage, the percent-
age of available battery capacity, number of battery modules
that are installed, number of battery modules that are bad,
and the predicted run time. Use this screen to check the sta-
tus of the battery modules. After the battery status screen
has been reviewed, press the Enter key. The power status
screen appears.
Note: If a battery module is diagnosed as bad, see Chapter 8.
Power Status Screen
Fig 7-10 Sample Power Status Screen
Power Status Screen - the reported Power Array capacity is
dependent upon the number of power modules installed and
the size of the frame. Use table 7-2 to confirm that the
PowerView is reporting the correct information.
Table 7-2 Symmetra
TM
Power Module/Frame Capacities
The power status screen also displays the actual level of fault
tolerance, the number of power modules installed in the
frame, and the number of bad power modules.
Fault Tolerance: The actual fault tolerance indicates the num-
ber of functioning power modules in the Power Array, minus
the number required to power the load. (i.e., If a load is 6kVA,
two modules are required. If five power modules are installed,
the fault tolerance will read N+3.) After this screen has been
reviewed, press the Enter key. The alarm threshold status
screen appears.