Step 7Step 7
Step 7Step 7
Step 7
: Review Diagnostic Information: Review Diagnostic Information
: Review Diagnostic Information: Review Diagnostic Information
: Review Diagnostic Information
The PowerView allows you to access an extensive set of diag-
nostics information. Follow this procedure to review the di-
agnostic screens.
The following sequence on the PowerView opens the diag-
nostics menu screen:
Fig 7-18 Opening the Diagnostics Menu Screen
Diagnostics Menu Screen
Fig 7-19 Diagnostics Menu Screen
Each line of the diagnostics menu screen contains a menu
selection item. Each of these opens a subsequent screen.
Fault & Diagnostics - This menu item displays an overview
of any faults detected within the system. If a fault is detected,
the PowerView will display the fault information. Otherwise
it will indicate that no fault was detected.
Intelligence Module - This menu item opens the main intel-
ligence module information screen.
Fig 7-20 Main Intelligence Module Information Screen
The status line at the top of this screen indicates if the main
intelligence module is functioning, and it provides detailed
information about the MIM.
Redundant Intelligence Module - This menu item opens the
redundant intelligence module information screen. It ap-
pears and functions the same as figure 7-20.
Power Module (Pwr Modules) - This menu item opens the
power module information screen.
Fig 7-21 Power Module Information Screen
With the flashing arrow cursor pointing at the first line (as
illustrated in figure 7-21), press the Enter key. The flashing
up/down arrow appears. Use the Arrow navigation keys to
scroll up or down. The status of each power module will
Chapter 7 - Configuring & Operating the Symmetra
TM
7-6
appear. In the event of a power module failure, use this menu
item to identify the failed power module. After a replace-
ment power module is installed, use this menu item to con-
firm that the new module is recognized by the Power Array,
and is functioning properly. (Procedure in Chapter 8.)
Battery Modules (Batts) - This menu item opens the battery
module information screen.
Fig 7-22 Battery Module Information Screen
With the selection arrow cursor pointing at the second line
(as illustrated in figure 7-22), press the Enter key. Note the
flashing up/down arrow appears. The status screen for the
battery module in the top battery module bay appears:
Fig 7-23 Top Battery Module Status Screen
This screen indicates that the battery module in bay R2 is
functioning properly. Use the Arrow navigation keys to scroll
through all of the battery module status screens. In the event
of a battery module failure, use this screen to identify the
failed module. After a battery module is replaced, use this
screen to confirm the new module is recognized by the Power
Array, and is functioning properly. (Procedure in Chapter
8.)
Step 8Step 8
Step 8Step 8
Step 8
: Review Logging Menu: Review Logging Menu
: Review Logging Menu: Review Logging Menu
: Review Logging Menu
The PowerView records the most recent 64 user or power
events in an electronic log.
The following screen sequence accesses the event log screen:
Fig 7-24 Open the Event Log Sequence
Event Log Screen
Fig 7-25 Event Log Screen
Scroll up or down through the log items using the Arrow
navigation keys. The time, date and the number of the selcted
log item is displayed on the top line. For more information
about a log item, select it, and press the Enter key.

Related product manuals