13.10.2 EMR Operation (Emergency Stop)
1. When it detects EMR signal, it stops soldering and RUNNING signal becomes LOW.
2. When it detects LOW of EMR signal, END signal is outputted.
3. When it detects RESET signal in the condition that EMR signal is High, READY signal becomes
High.
4. After READY signal became High, it is possible to start to solder by START signal.
When it detects LOW of EMR signal, the temperature control function also become OFF.
When READY signal becomes High, it starts to control the temperature again.
* It is not necessary that START signal is outputted as a pulse. (Except for LAN operation)