FIGURE 1 – Run Wire for System
RUN THE REQUIRED WIRES AND MOUNT THE SYSTEM COMPONENTS
1. Determine component locations.
2. Run and label wires. Use FIGURE 1 for selecting wire type.
3. Mount components as specified in each product’s installation instructions.
Maximum Wiring Distances
From To Maximum Distance
Automation or Computer System Protocol Adapter 3 ft. Cable Provided with Protocol Adapter
Protocol Adapter Thermostat (this includes going through the Distribution Panel) 4000 ft. (cumulative)
Thermostat Support Module 1000 ft. (cumulative)
Support Module Temperature Sensor Option 300 ft.
Thermostat Temperature Sensor Option 300 ft.