QS1 Installation/User Manual
18
8.Technical Data
SA10: Low/High Frequency Ride Through (L/H FRT) and Must Trip Settings
Region
Range
of Adjustability
(Hz)
Ride-Through
Until (s)
Ride-Through
Operational
Mode
Trip Time
(S)
Range of
Adjustable Trip
Time Default (s)
High Frequency 2 (HF2)
High Frequency 1 (HF1)
Near Nominal (NN)
Low Frequency 1 (LF1)
Low Frequency 2 (LF2)
62.0 - 64.0
60.1 -[62.0, 64.0]
Not Applicable
[53.0,57.00] - 59.9
53.0 - 57.0
No Ride-Through
299s
Indefinite
299s
No Ride-Through
Not Applicable
Mandatory Operation
Continuous Operation
Mandatory Operation
Not Applicable
0.16s
300s
Not Applicable
300s
0.16s
0.1-0.5
0.16-600
N/A
0.16-600
0.1-0.5
SA11: Ramp Rate (RR) and Soft Start (SS)
Units
Adjustment Range
Tolerance
Max
Min
Ramp-up rate
%Irated/s
100
1
+/- 2%
Soft start ramp rate
%Irated/s
100
1
+/- 2%
SA12: Specified Power Factor (SPF)
Adjustment Range
Max
Min
Inductive, under excited, power factor
-0.8
-1.0
Capacitive, overexcited, power factor
1.0
0.8
SA13: Volt/VAr Mode (VV)
Units
Data
AC power
W
1200
Reactive power absorption (inductive, under excited)
VAr
360
Reactive power production (capacitive, overexcited)
VAr
360
Deadband
Vnom
0.967-1.033
SA14: Frequency-Watt (FW)
Output Power Rating[W]
1200
Manufacturer's stated P(f) accuracy [W or %W]
5%Prated
Maximum slope of frequency droop [%Prated/Hz]
200
Minimum slope of frequency droop [%Prated/Hz]
40
SA15: Volt-WattVW
Output Power Rating[W]
1200
Output Power accuracy [W or %W]
5%Prated
Maximum Slope of active power reduction[%Prated/V]
40
Minimum Slope of active power reduction[%Prated/V]
8