Function code 05H send format Instruction
Type Number of bits Example
The function writes a discrete
amount to the remote device.
Slave address 1 01H
Function code 1 05H
Data
area
Start
address
2 003AH
Discrete
quantity
2 FF00H
CRC check 2 AC37H
Function code 05H response format Instruction
Type
Number of
bits
Example
The normal response format is a
copy of the request.
Slave address 1 01H
Function code 1 05H
Data
area
Start
address
2 003AH
Discrete
quantity
2 FF00H
CRC check 2 AC37H
Function code 06H send format Instruction
Type
Number of
bits
Example
The function writes a 16 bit
register value to the remote
device.
Slave address 1 01H
Function code 1 06H
Data
area
Start
address
2 008CH
Register
value
2 003CH
CRC check 2 4830H