HC151+ pH(Rx)-Cl(J) / HC200+ pH(Rx)
ENGLISH
Setpoint Redox:
Setpoint of Chlorine:
Es. Chlorine:
Setpoint: 1.20 ppm
Window width limit: 0.80 ppm (es. 120 strokes/minute);
For values equal to or higher than the Setpoint, the pump is stopped;
The pump works at maximum frequency for values equal to or lower than
the set window width limit, the frequency decreases as the Setpoint value
approaches.
ATTENTION: the pump can also be programmed for the
dosage of a Reductive chemical product but it is necessary to
check that the seals in the pump body are chemically
compatible with the product to be dosed.
Es. Redox: dosing of an OXIDANT
chemical:
Setpoint: 750 mV
Window width limit: 650 mV (es. 120
strokes/minute);
For values equal to or higher than the
Setpoint, the pump is stopped;
The pump works at maximum frequency for
values equal to or lower than the set
window width limit, the frequency
decreases as the setpoint value
approaches.