Flex ECO 6S/X MRX Instruction Manual
August 2017 v1.0
Page 21 of 34
ON DIP ON DIP
PB1 2
~
PB3 4
~
PB5 6
~
S1 DIP 1~10
ON DIP ON DIP
S2 DIP 1~5
4.2.3 Dipswitch Settings
4.2.3.1 Interlocked Pushbutton Pair
Interlocked means any pushbutton pair can not be pressed simultaneously as it will
cancel each other out. Interlocked setting usually applies to electric motor’s forward &
reverse motion and On & Off switches. Five dip positions correspond to a pushbutton
pair.
Dip Settings Function
00000
Single speed only
00001
3 output relays Closed/Closed relay action at 2
nd
speed
(shared 2
nd
speed output relay)
00010
On (right button) & Off (left button)
00011
Magnet Lift On & Off
00100
On (right button) & Off (left button)
(EMS → all relays deactivates when STOP button is pressed)
00101
On + Start/Off + Start - For added safety, you must first
press and hold the START button and then press the
On or Off pushbutton to activate the output relay.
00110
FWD/REV toggled
00111
FWD/REV toggled
(EMS → all relays deactivates when STOP button is pressed)
01000
Single speed + External warning*
01001
3 output relays Closed/Closed relay action + External warning*
01010
3 output relays Closed/Closed relay action + Brake
01011
3 output relays Closed/Closed relay action + Brake + External warning*
* External warning function requires installing an external warning device such as horn and lights to
the K10 Function output relay.