4.6.2 Relay outputs:
2 relay outputs
Hysteresis independently programmable in the display unit.
Time delay independently programmable from 0 to 25 s, in 0.1s increments.
NO-NC contact 8 A - 250 V on resistive load
Activation or de-activation of alarm x
The status of relay x depends on the performed programming
The relay x remains still
rEL.1
rEL.2
AL.X
On
OFF
Choice of the operating mode:
Mode setpoint
OFF
ON
setpoint
Legend:
ON coil supplied
OFF coil not supplied
or
ModE.x
setpoint
OFF
ON
SPX SPX
Choice of the setting unit of the setpoints and hysteresis
setpoints and hysteresis in input scale points
setpoints and hysteresis in display points
InPut
diSPL.
PArA.
Mode window
Mode setpoint
Mode window
Choice of the status of the relay associated led
The led indicates the alarm state
Led lit when relay active (coil supplied)
Led still when relay active (coil supplied)
Setting of the hysteresis in display points
The hysteresis is active on switching from lit led to still led, that is to
say on switching out of alarm, as the led represents the alarm state.
OFF
OFF
OFF
ON
ON
ON
setpoints
setpt
setpt
or
SP.X
SP.X
- HYSx
HySt.x
LEdx
On
OFF
SP1.X
SP1.X
-HYSt.x
SP2.X
SP2.X
+HYSt.x
SP2.X
SP1.X
SP2.X
SP1.X
led lit
led lit
led still
led still
led still
Time delay on the alarm
The relay time delay is adjustable from 000.0 to 025.0s. in 0.1s
increments. It is active both on switching and switching off.
tiME.x
Recording of the alarms
Allows recording the alarm after a setpoint has been passed. When the
measure reverts below the alarm setpoint, the relay remains on and the
led blinks to warn the user that a setpoint has been passed (to reset the
alarm recordings to 0 see menu ).
Note: An exit from mode programming with saving of the configuration
will reset the alarm recordings to zero.
Display of the alarm messages
A programmed alarm message can be made to appear alternating with
the measure. The message will appear only during the alarm, while the
associated led is lit.
Setting of the setpoints: there are 2 ways to adjust setpoints:
- either in mode programming entering the correct access code,
- or by pressing simultaneously on
and if the access to a quick
entering has been authorized on the programming of the code (see p18).
MEM.x
CLEAr
MESSx
M