4.4.2 Programming of the display factor
diSPL.
inputs process, resistance, potentiometer
place of the decimal point
«
rESOL.
--.--
display resolution
1 or 1/10th of degree
temperature input
setting in display points (or in input
points if SCALE NO is program-
med) of the same number of ordi-
nates “bxx” and abscisses “Axx”
if SCALE YES :
Y00 = dDIS and YNB-1 = F.DIS
according to options
IntEG: coefficient from 0 to
integration indice
AnA.
rELAy
SECU
«
0000
or
or
«
«
DISP
From 3 to 20 : represents the
number of points (including
the down and full input scale)
Xoo=dinp
XNB-1=F.INP
«
IntEG.
«
«
1
o
0.1
o
«
Point
«
Funct.
«
Li.SPE
«
LinEA.
«
«
nb
«
function special
linearisation
«
0020
«
-88.88
«
-88.88
«
A19
«
A00
«
-88.88
«
F.in
«
-88.88
«
d.diSP
«
-88.88
(1)
in mV, V or mA
according to the
type
full scale
in mV, V or mA
according to the
type
display corres-
ponding to the
input down scale
«dInp»
«
F.diSP
«
-88.88
display corres-
ponding to the
input full scale
«F.INP»
(1)
-2< x < 22.00 (mA)
-1< x <11.00 (10V)
-30< x < 330.0 (300 V)
-10< x < 110.0 (100mV)
-0.1< x < 1.100 (1V)
(1)
«
d.in
linear function
down scale
b00
«
-88.88
«
Cut.oF
b19
«
-88.88
no
«
«
yES
«
-88.88
(1)
(1)
setting in display points
You can choose to assign the analog output to the input measure (PArA InPut) or to the displayed measure
(PArA diSPL.).
Eg.: with PArA diSPL
• When the transmitter indicates 20°C the value of the analog output will be 4 mA
• When the transmitter indicates 100°C the value of the analog output will be 20 mA
Eg.: with PArA InPut
• When the value of the current measured on the input is 6.0 mA, the value of the analog output will be 4 mA
• When the value of the current measured on the input is 20.0 mA, the value of the analog output will be 20 mA
«
-88.88
AnA
down scale of the analog output
According to the equipped
output type
full scale of the analog output
display corresponding to the output down scale
display corresponding to the output full scale
according to options
rELAy
SECU
or
See also the features of the outputs p11
(4)
00.00 < x < 22.00 (mA)
00.00 < x < 11.00 (V)
(4)
(4)
«
-88.88
«
-88.88
«
-88.88
«
d.out
«
F.out
«
FO.diS
«
tyPE
AnA.
«
«
OUt.U
OUt.i
«
d.out
«
F.out
«
dO.diS
«
FO.diS
Upwards move / increase
Validation / vertical move
Downwards move /
decrease
Menu exit / access
M
PArA
InPut
diSPL.
«
dO.diS
= 4 mA
= 20,00mA
= 20,0°
= 100,0°
InPut
= mA
«
d.out
= 4 mA
«
F.out
«
dO.diS
«
FO.diS
= 20 mA
= 6,0 mA
= 20,00 mA
4.4.3 Programming of the analog output (if option)