P92x/EN CT/E11 Technical Guide
Courier Database
Page 94/118 MiCOM P921-P922-P923
Col Row Menu Text Data Type Ind
Values
(* : default)
Depend Cell Type Min/Max/Step
03 Threshold V0> Courier floating point number
5.0 V * if 1000KV Range
else 20.0 V
4202=1 Setting
5.0 / 130.0 / 0.1 if 1000KV
Range
else 20.0 / 480.0 / 0.5
04 Delay Type Indexed String 0
1
0: definite time *
1: inverse time
4202=1 Setting 0/1/1
05 TMS Courier floating point number 1.0 * 4204=1 Setting 0.5/100.0/0.5
06 T RESET Courier floating point number 0.1 s * 4204 = 1 Setting 0 / 1000.0 / 0.1 s
07 Delay V0> Courier floating point number 0.04 s * 4204=0 Setting 0 / 599.9 / 0.01 s
08-0F Reserved
10 Stage 2 Overvoltage (Sub Heading)
11 Max V0>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
12 Threshold V0>> Courier floating point number 5.0 V * if 1000KV Range
else 20.0 V
4211=1 Setting 5.0 / 130.0 / 0.1 if 1000KV
Range
else 20.0 / 480.0 / 0.5
13 Delay V0>> Courier floating point number 0.04 s * 4211=1 Setting 0 / 599.9 / 0.01 s
14-1F Reserved
20 Stage 3 Overvoltage (Sub Heading)
21 Max V0>>> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
22 Threshold V0>>> Courier floating point number
5.0 V * if 1000KV Range
else 20.0 V
4221=1 Setting
5.0 / 130.0 / 0.1 if 1000KV
Range
else 20.0 / 480.0 / 0.5
23 Delay V0>>> Courier floating point number 0.04 s * 4221=1 Setting 0 / 599.9 / 0.01 s
43 00 V2 (Vinverse) OVERVOLTAGE
01 Stage 1 Overvoltage (Sub Heading)
02 Max V2> Binary (1 bit) 0 Disabled * / Enabled Setting 0/1/1
03 Threshold V2> Courier floating point number 130.0 V * if 1000KV Range
else 480.0 V
4302=1 Setting 5.0 / 200.0 / 0.1 if 1000KV
Range
else 20.0 / 720.0 / 0.5
04 Delay Type Indexed String 0
1
0: definite time *
1 : inverse time
4302=1 Setting 0/1/1
05 TMS Courier floating point number 1.0 * 4304=1 Setting 0.5/100.0/0.5
06 T RESET Courier floating point number 0.1 s * 4304 = 1 Setting 0 / 1000.0 / 0.1 s