19ExTensor
Automatic operation (AUTO mode, switch position "AUTO"):
The actuator runs with an external signal, which is present depending on the setting on the terminal clamps, the signal clamps or
CAN clamps. The onboard buttons are without function.
Manual mode (MANU mode, switch position "MANU"):
The actuator can run left and right by using the buttons "L" & "R", if the actuator is not in setup mode. Change to setup mode by
pressing the MENU button longer than >1s.
Setup mode (Switch position "MANU"):
Different actuator parameters can be set up and adjusted.
Start setup mode:
1. Slide switch to position"MANU"
2. Press button MENU longer than >1s
Setup mode is turned on and the rst menu item "MAIN MENU" is displayed.
Within the setup menu navigate between different menu items and adjustments by pressing the buttons "L" & "R".
Conrm any entry by pressing the MENU button (press <0.5s).
Exit any menu item by pressing the MENU button longer than >1s.
Exit setup mode:
Exit the setup mode by moving the slide switch to position "AUTO" and conrming the notication message.
Alternatively press the MENU button in the top menu layer longer than >1s and conrm the notication message. The actuator
then changes to manual mode (MANU mode).
A warning message is displayed when switching between different operating modes,
because the actuator can run under certain conditions. Conrm the message with the MENU
button.
The actuator may run and move the connected valve when switching from MANU to AUTO
and you conrm the warning message.
After switching from MANU to AUTO and conrming the warning message the actuator can
be operated by using the buttons "L" & "R".
ADVICE
!
WARNING