20
installation
Fitting the Coaxial Flue (Ø 60 / 100 Vertical)
Note: See table for maximum and minimum ue
runs.
Contents:
1x Silicone O-Ring (60mm)
1x Conical Adaptor (60/100mm)
1x Vertical Flue Kit (80/125mm)
3x Screws
The vertical ue kit is supplied with a specially de-
signed weather proof terminal tted, which can be
used either with a at roof or a pitched roof.
The vertical ue kits useable lengths with the
pitched roof ashings are indicated in Fig. 7.
Before proceeding to t the ue, ensure that the
maximum ue length has not been exceeded (see
the tables) and that all elbows and bends have been
taken into consideration. For each additional 90°
elbow 1 metre must be subtracted from the maxi-
mum ue length, and for each 45° 0.5 metres must
be subtracted from the maximum ue length (the
height of the vertical adaptor and a 45° bend can be
seen in Fig. 8).
Mark the position of the ue hole in the ceiling
and/or roof (see Fig. 7 for distance from wall to the
centre of the ue).
Cut a 130mm diameter hole through the ceiling
and/or roof and t the ashing plate to the roof.
DO NOT cut the vertical ue kit.
To connect the vertical ue kit directly to the boiler,
place the vertical starter kit (Part No. 3318079) (see
Fig. 7) onto the exhaust manifold and secure with
the clamp, t the vertical adaptor onto the vertical
starter kit (Note: there is no need to use a clamp to
secure this as it is a push t connection), the vertical
ue kit must then be inserted through the roof
ashing, this will ensure that the correct clearance
above the roof is provided as the terminal is a xed
height.
Should extensions be required, they are available
in 1 metre (Part No. 3318077) and 500mm (Part
No. 3318078) lengths. They must be connected
directly to the vertical starter kit before connec-
ting the adaptor to allow the vertical ue kit to be
tted. In the event that extension pieces need to be
shortened, they must only be cut at the male end
and it must be ensured that the inner and outer ue
remain ush.
When using the vertical ue system, action must be
taken to ensure that the ue is supported adequa-
tely to prevent the weight being transferred to the
appliance. Use 1 ue bracket per extension.
When the ue passes through a ceiling or wooden
oor, there must be an air gap of 25mm between
any part of the ue system and any combustible
material. The use of a ceiling plate will facilitate this.
Also when the ue passes from one room to another
a re stop must be tted to prevent the passage of
smoke or re, irrespective of the structural material
through which the ue passes.
180 mm
Total length
of Vertical Kit
1355 mm
Useable length
of Vertical ue
690 mm*
Fig. 7
Fig. 8