1-2. Ice making mode
NO
NO
YES
YES
NO
YES
YES
NO
1)
2)
3) In case of ice-sensor error, ice making stops after 4.8 hours.
Ice making stops if ice-sensor is below -12.5 degree after 130 minutes.
Ice making also stops if ice-sensor is below -9.5 degree for 15 minutes, though
ice-sensor is not below -12.5 degree after 130 minutes.
2. Ice separating (drop) mode
status of
Ice tray
Normal level SW
Level SW
Motor revolution
.
Level SW error
8-11 Max 1.1
8.5-12.2
0.2
10
11
1.1
1) Time of each zone is used to verify level switch error.
2) The rotation of motor is sensed at each zone.
3) In case of level switch error, ice separation is done by time.
4) If ice separating motor has error, the mode stop.
START
130 min passed?
I-S<-12.5
Ice separating mode
I-S<-9.5
15 min passed?
C
C
Ice separation start Horizontal position
sec sec secsec
sec
sec
sec
clockwise counterclockwise stopc.w